Safety Considerations
The following definitions are used as safety considerations on the
Evergreen IM motor and in this manual. Please read and observe all
of these safety concerns.
SAFETY
SYMBOLS
Installation and service of this motor should be attempted only by
trained service technicians familiar with the Evergreen instructions
and training manual.
This motor should be installed in accordance with accepted practices
and installation instructions, and in compliance with all national and
local codes.
REG7232_EvergreenIM_Reprint.indd 1 4/28/10 2:05:19 PM
Always disconnect the main power from the unit prior to servicing the pool
pump lter motor. It is also good practice to conrm the power is o with a
voltage meter.
Two Speed Connections with Timer
If you had a single speed motor prior to this installation, you will need to run a
newconduitwithfourconductors(HighSpeed,LowSpeed,Neutral,andGround)
and proceed through the following steps to properly operate the motor with the
multi-speed timer. Proceed to step 5 if a multi-speed timer is already installed and
operating a two-speed induction motor.
Step 1: Remove the caution / instruction cover from the front of the timer,
exposingthescrewterminalsunderneath(refertoFigure8).
Step 2: Connect the L1 and L2 incoming power leads into the two left-most
screw terminals . The timer is connected for 240V from the factory, so
no internal timer changes are required.
Step 3: Connect a jumper lead of at least 18AWG size between the L1 terminal
and the Line-side of Circuit 1. Connect a second jumper lead between
the Load-side of Circuit 1 and the Line-side of Circuit 2 as illustrated
above.
Step 4: Connect the L2 lead of the new four-conductor conduit to the same
screwterminalastheincominglineL2,theHighSpeedBlackleadto
the Line-side of Circuit 1, and the Low Speed Red lead to the Load-side
of Circuit 2.
Figure 8
Figure 9