Installation guide
22 23
22 23
Software Error Code Matrix
The imPower control panel has a red error display LED to indicate operation
issues.NormaloperationisindicatedbyasingleashofthisLEDuponstartup.
Any subsequent blink sequence of this LED indicates that a fault has been
registered by the motor control, with the explanation of these faults given in
the below table. This table also includes the cause for this fault as well as some
potential actions to potentially resolve the issue.
Blinks Faults Software Cause Action
1 Micro
controller
failure
Micro controller
is continually
rebooting.
Noactioncanbetakento
resolve issue. Return motor for
warranty.
2 Under
voltage
The line voltage has
dropped below 180
volts AC running.
- The controller will reboot
after voltage comes above 209
volts AC for at least 6 seconds.
- Reduce distance between
motor/pump and breaker.
- Turn o any other non-
critical equipment on the
same breaker circuit.
3 Temperature Internal electron-
ics detected an
over temperature
condition (+100C on
sensor)
- Verify the proper impeller has
been applied (net 1.25Hp max)
- Turn the power o at the
timer / breaker and allow mo-
tor to remain o for at least
15 minutes before reapplying
power.
4 Over current
trip
Over current
protection has
tripped.
- Verify the proper impeller has
been applied (net 1.25Hp max)
- Inspect all equipment /
piping in the system
connected to the pump
5 Over voltage The line voltage has
risen above 269 volts
AC
- The controller will reboot
after voltage comes below 254
volts AC for at least 6 seconds.
- Check any other equipment
on the same breaker circuit.