Blinks Faults Software Cause Action
6 Output shaft
seized
Motor failed to start.
Motor was stopped.
- Manually rotate the shaft
via the shaft access in the fan
cover
- Inspect all equipment
in-line with the pump for
obstructions or locked pump
parts.
7 Self check One or more of
the self-tests failed
either at start up or
while running.
- Turn the power o at the
timer / breaker and allow
motor to remain o for at least
15 minutes before reapplying
power.
- Return motor for warranty if
error persists.
8 Motor fault One or more of the
phases has become
disconnected.
- Turn the power o at the
timer / breaker and wait one
minute before opening the
topside connection enclo-
sure. Verify phase leads from
both the motor and control
connecting into the terminal
block (red, yellow, white leads
on left-most connections of
blocks as viewed from the
conduit entrance) are properly
connected and screws on the
terminal block are tightened
suciently.