Installation guide
6 7
6 7
Operation
imPower motors are congured with Constant Speed, meaning they simply maintain
the speed (RPM) they are congured for in each application. This reduces the eect
lter cleanliness and product load have on the operation of the motor, unlike
traditional induction motors. The motor only uses the power (current) necessary to
operate at its programmed speed, and has the ability to automatically increase or
decrease power to maintain that speed.
imPower motors turn on and o with application of line voltage. This is critical to its
eectiveness with all existing line-power cuto timers and automation controllers.
Start up
During start up, motor current is slowly applied to motor windings. This provides a
controlled smooth start up. The motor/pump will accelerate to the high speed level
of 3450 rpm in approximately 6-8 seconds. Once started, the motor is programmed to
operate on high speed for two minutes to assure a proper prime is achieved, during
which time no attempt to change speeds will be recognized. Only after this two-min-
ute cycle will a change speed signal be accepted.
If no speed change signal is received by the motor after the two-minute prime cycle,
the motor will remain on high speed for a total of two hours, then automatically turn
down to one of the two reduced speeds. The factory default reduced speed setting
is “low” (1725 rpm), though this can be modied to “medium” (2600 rpm) if the ow/
pressure at low is deemed insucient for operation of certain poolside equipment/
features. The modication of the reduced speed automatic turn-down is found on
page 20 of this guide, titled “Automatic Reduced Speed Selection”.
Stall Detect (Locked Rotor Protection)
This feature protects the motor from external obstructions in the event it does not
achieve high speed operation within 15 seconds of applying voltage or if the RPM
drops below 500 RPM during operation. The imPower is programmed with a hard
fault feature such that the motor will automatically shut down if a stall detect fault
is registered. Power at the timer or automation controller must be removed and
reapplied after one minute of “dwell” time to restart the motor.
Overload Protection (Over-Current or Over-Temperature)
The imPower motor is specied with a series of sensors that continuously monitor the
temperature of critical internal components as well as the current owing through the
electronics. The motor will automatically shutdown if either limit is exceeded. Like the
stall detection, the timer or controller power must be removed, though it is recom-
mended that the motor power stay removed for at least 15 minutes to allow the motor
to cool and/or to determine the cause of the overload condition.