Cut Sheet

Product Data Sheet
Wire Range:
Line side: (1) 2/0 - #14 AWG
Load Side: (4) #4 - #14 AWG
See tables below for SCCR wire ranges, flexible
stranded and multiple wire approvals.
Electrical Ratings:
•175A copper wire, 135A aluminum wire (Based on NEC Table 310-16, 7C columns)
•600 Volts AC/DC (UL 1059 Class C, User Group - General Industrial)
• Factory and Field Wiring
Short Circuit Current Ratings (Copper wire only):
SCCR, RMS Volts
SYM Amps Max
Line Load J T RK1 RK5 G CC
2/0 - 6 4 - 14 200 200 200 100 60 30 100,000 600
SCCR, RMS Volts
Line Load SYM Amps Max
2/0 - 1 4 - 10 22,000 480
2 - 4 4 - 12 22,000 480
2 - 6 4 - 14 30,000 480
6 14 50,000 480
Square D JGL36250 250 35,000 480
2/0 - 10 4 - 10
Square D JJL36250 250 65,000 480
Square D JLL36250 250 65,000 480
Square D JDL36250 250 18,000 480
Suitable Overcurrent Protection Fuse Required
Class/Max Amp Rating(kcmil/AWG)
Overcurrent Protection Circuit Breaker Required
Mfr Type Max Amp
Allen Bradley 250140U-J3D3
140U-J6D3
Allen Bradley
Allen Bradley
Allen Bradley
140U-J3D3
140U-J6D3
250
140U-H3C3 125
140U-H6C3 125
Mechanical Ratings:
• Maximum insulator base temperature: 150°C (302°F)*
• Storage and transportation temperature range: -35°C to 125°C (-31°F to 23F)*
142X570
Replace “X” with 1, 2 or 3 for number of circuits
Distribution Power Block
175 Amps, 600 Volts
(AC/DC)