TorMinal GB Operating Instructions 20310V001-052006-0-OCE-Rev.
A A.2 A.3 A.4 A.1 A.5 ON B B.1 B.2 B.3 B.
! Caution ! Valid as from control versions: - duo 500 SL, sprint 550 SL, duo 650 SL: . . . . . . . . ver 015 - marathon 550 SL, 800 SL, 1100 SL: . . . . . . . . . . . ver 017 - twist 200: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ver 030 - stargilder 300: . . . . . . . . . . . . . . . . . . . . . . . . . . . . ver 012 - marathon tiga 800 SL, - 1100 SL: . . . . . . . . . . . . . ver 010 - starglider 300 E: . . . . . . . . . . . . . . . . . . . . . . . . . . . ver 010 - gator 400: . . .
Contents Table of Contents ............................................................2 Symbols Safety Instructions Normal Use Supplied Components Technical Data Display of control version 2 2 3 3 3 4 Description of Function ..................................................6 Switching on the TorMinal Connecting TorMinal to a control unit 7 7 Operation of Gate ............................................................7 Explanation of Terms ......................................................
General information Symbols Symbol indicating potential danger! Failure to follow instructions may result in serious injury to persons or damage to the drive mechanism! Information, useful tip. A.1 (1) Refers in the introduction or in the body of the text to the corresponding illustration. General Safety Instructions • These Operating Instructions (BA) must be read, understood and observed by the person using the TorMinal.
General information Correct use • • Any malfunction constituting a safety risk is to be eliminated without delay. The TorMinal may only be connected to the following drive mechanisms operated via SOMMER - sprint 550 SL - duo 500 SL, duo 650 SL - marathon 550 SL, 800 SL, 1100 SL - twist 200 + DSTA24 - starglider 300 - marathon tiga 800 SL, 1100 SL - starglider 300 E - gator 400 - jive 200 + DSTA24-UF • • • • SOMMER accepts no liability for changes made to the settings of any given control unit.
General information Display of control version Note! The correct display of the control version of the drive system depends on the TorMinal software version. If an incorrect control version is displayed (e.g. Test PCB), you can nevertheless make the necessary modifications. To update the TorMinal software, return the TorMinal to SOMMER free of charge. TorMinal with software version 1.00 Drive Top display Bottom display sprint/duo SL Sprint e.g.: V0xx.000 marathon SL Marathon e.g.: V0xx.
General information TorMinal with software version 1.30 and higher Drive Top display sprint/duo SL sprint Bottom display e.g.: V0xx.000 marathon SL marathon e.g.: V0xx.000 twist 200 DSTA24 e.g.: V0xx.000 starglider 300 STA24 e.g.: V0xx.000 marathon tiga SL tiga e.g.: V0xx.000 starglider 300 E STA1 e.g.: V0xx.000 gator 400 STA1 e.g.: V0xx.000 jive 200 DSTA24 e.g.: V0xx.
Description of Function A+B Components and their respective functions The TorMinal is used to check or change the values set on SOMMER drive control units. A.1 ON/OFF switch Switches the TorMinal ON or OFF. A.2 Display The display comprises 2 x 8 characters. The upper line displays the given memory slot (Mem) and its number whilst the lower line shows the corresponding setting (Val). A.3 Connecting cablel This cable connects the TorMinal with the given control unit.
Operation Safety instructions ! Important to note ! Before any change to the settings, reset the control system (deletion of force values, for details see installation and operating manual of your operator). Reset with the TorMinal is not sufficient, as the force values are not deleted and only the parameters that can be adjusted with the TorMinal are reset to the factory values. The control unit has to relearn the running times and required forces.
Operation Changing and memorising settings When the setting has been changed, the preceding "s" disappears. This indicates that the setting has been changed but not yet memorised. Procedure : 1. Select required memory slot (Mem) by pressing buttons Mem + or Mem - , see "Memory Slots and their Respective Functions" section. 2. Change setting by pressing buttons Val + or Val - . 3. When the required value has been set, this is memorised by pressing button once.
Explanation of Terms Used The TorMinal can be used to set SOMMER's new drive mechanisms to suit almost all types of gate/door. The illustration here shows the drive unit's speed curve (default setting without 2) when opening or closing a gate/door. 2 8 1 7 5 6 4 2 1. Maximum speed The drive mechanism's top speed - separately adjustable for opening and closing. 2. Soft run mode Can be additionally selected and separately adjusted: - when the drive mechanism leaves its end CLOSE + OPEN positions.
Explanation of Terms Used 7. Zero line 8. Max. line The maximum speed that can be set. The speed setting range lies between the zero line and the max. line. Travel time The time the drive mechanism needs to close or open a gate/door. Cycle counter Cycle = movement, comprising one complete opening and closing movement between the end travel positions. Only when the gate/door reaches the gate/door end CLOSE position is a cycle counted.
Memory Slots and their Respective Functions This is where the settings of the individual memory slots can be read. The first column displays the memory slot concerned, the second the available setting range (the first number is the lowest and the second number the highest possible setting), the third column describes the given slot's function and the fourth column the given slot's default setting.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val 019 15 - 60 Description of respective functions Soft run speed when opening Default setting = Val sprint / duo SL 25 020 15 - 60 Maximum speed when opening 55 4) Note! Memory position (020) can only be modified after the control system has been reset (force values deleted). Such a system reset cannot be completed with the TorMinal software.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val 035 0 - 15 Description of respective functions Switching soft run ramps ON or OFF Default setting = Val sprint / duo SL 15 This function enables the soft run ramps to be switched ON or OFF individually.
Memory Slots and their Respective Functions marathon 550 SL, 800 SL, 1100 SL Memory slot Mem Setting range Val 003 Force taught when opening gate/door (OPEN) 004 - 1) - 1) Force taught when closing gate/door (CLOSE) 255 3) 255 3) 005 - 1) Travel time when opening gate/door (OPEN) 255 3) - 1) Travel time when closing gate/door (CLOSE) - 2) Cycle counter (Z1) - 2) Cycle counter (Z2): counts from 0 to 255 006 011 012 013 0 - 255 Description of respective functions Value in steps of 0.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val Description of respective functions Default setting = Val marathon SL 021 0 - 40 Start of soft run ramp for gate/door end OPEN position 15 Start of soft run ramp prior to drive mechanism moving into gate/door end OPEN position. Adjustable in steps of 0.25 seconds.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val 035 0 - 255 Description of respective functions 1. Switching soft run ramps ON or OFF Default setting = Val marathon SL 31 This function enables the soft run ramps to be switched ON or OFF individually.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val 036 0 - 31 Description of respective functions Default setting = Val marathon SL Special functions 2 0 4) Note! Memory position (036) can only be modified after the control system has been reset (force values deleted). Such a system reset cannot be completed with the TorMinal software. 1. Dead man mode only via button 1 + 2 By pressing button 1, the gate opens; by pressing button 2, the gate closes.
Memory Slots and their Respective Functions twist 200 + DSTA24, jive 200 + DSTA24-UF Memory slot Mem Setting range Val 002 - 2) Cycle counter (Z1) - 2) Cycle counter (Z2): counts from 0 to 255 - 1) - 1) Travel time for gate/door wing 2 to open Travel time for gate/door wing 1 to open 008 - 1) - 1) 013 - 1) Force taught when opening gate/door wing 2 014 - 1) - 1) Force taught when closing gate/door wing 2 - 1) 0 - 40 Force taught when closing gate/door wing 1 003 005 006 007 015 016 021
Memory Slots and their Respective Functions Memory slot Mem Setting range Val Description of respective functions Default setting = Val twist 200 + DSTA24 jive 200 + DSTA24-UF 028 8 - 40 Duration of delay in closing gate/door wing 2 20 The period after which gate/door wing 2 reaches gate/door end CLOSE position after gate/door wing 1 has already reached this position Adjustable in steps of 0.25 seconds.
Memory Slots and their Respective Functions starglider 300, starglider 300 E, gator 400 Memory slot Mem Setting range Val Description of respective functions Default settings = Val starglider 300 + 300 E, gator 400 003 Programmed force for gate opening (OPEN) 004 - 1) - 1) Programmed force for gate closing (CLOSED) 255 3) 255 3) 005 - 1) Runtime of gate opening (OPEN) 255 3) - 1) Runtime of gate closing (CLOSED) - 2) Cycle counter (Z1) - 2) Cycle counter (Z2) counts from 0 to 255 006 01
Memory Slots and their Respective Functions Memory slot Mem Setting range Val Description of respective functions Default settings = Val starglider 300 + 300 E, gator 400 021 0 - 40 Start of soft run ramp for end position gate OPEN 15 Start of the soft run ramp before drive moves gate to end position OPEN. Adjustable in steps of 0.25 seconds.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val 035 0 - 255 Description of respective functions 1. Switching soft run ramps on/off Default settings = Val starglider 300 + 300 E, gator 400 26 This function allows you to individually switch on or off soft run ramps.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val Description of respective functions Default settings = Val starglider 300 + 300 E, gator 400 036 0 - 31 Special functions 2 0 4) Note! Memory position (036) can only be modified after the control system has been reset (force values deleted). Such a system reset cannot be completed with the TorMinal software. 1.
Memory Slots and their Respective Functions marathon tiga 800 SL + 1100 SL Memory slot Mem Setting range Val Description of respective functions Default setting = Val marathon tiga SL 003 Force taught when opening gate/door (OPEN) 004 - 1) - 1) Force taught when closing gate/door (CLOSE) 255 3) 255 3) 005 - 1) Travel time when opening gate/door (OPEN) 255 3) - 1) Travel time when closing gate/door (CLOSE) - 2) Cycle counter (Z0) - 2) Cycle counter (Z1): - 2) Cycle counter (Z2) counts fr
Memory Slots and their Respective Functions Memory slot Mem Setting range Val Description of respective functions Default setting = Val marathon tiga SL 021 0 - 40 Start of soft run ramp for gate/door end OPEN position 15 Start of soft run ramp prior to drive mechanism moving into gate/door end OPEN position. Adjustable in steps of 0.25 seconds.
Memory Slots and their Respective Functions Memory slot Mem Setting range Val 031 2 - 255 Description of respective functions Gate open time Default setting = Val marathon tiga SL 30 Adjustable in steps of 1 second. 032 0 - 255 Clearing time 40 Adjustable in steps of 0.25 seconds 033 0 - 255 Back jump 20 Adjustable in steps of 1 millisecond. 034 4 - 255 Reversing period 8 Duration of reversing period when safety input has been tripped or when automatic power cut-off occurs.
Miscellaneous Troubleshooting Fault/Behaviour - Cause/Message on display Display does not work - TorMinal switched off - Display defective - TorMinal dropped on floor - Battery flat - Display is black Message on display - ! No PCB ! Possible remedial action - Switch TorMinal on Replace TorMinal Replace battery Connecting cable plugged in incorrectly - No control unit connected - Connecting cable (A.
Miscellaneous Warranty and After-sales Service The warranty extended complies with the relevant statutory regulations. Your contact for possible warranty claims is your specialist retailer. The warranty only extends to the country in which the TorMinal was purchased. Batteries, fuses and filament lamps are not covered by the warranty. If you require after-sales service, spare parts or accessories, please contact your specialist retailer. We have tried to make the operating instructions as clear as possible.
SOMMER Antriebs- und Funktechnik GmbH Hans-Böckler-Str.