Table 7: Versa-Crimp
®
Compression Lug Kits — Aluminum
Panelboard Amps Kit Catalog Number Wire Range Crimp Tool
125 NFALV1
#4–300 kcmil
21.15–152 mm
2
VC6
250 NFALV2
250–350 kcmil
126.7–177.3 mm
2
400 NFALV4
(2) 2/0–500 kcmil
(2) 67.43–253.4 mm
2
600 NFALV6
Table 8: Versa-Crimp
®
Compression Lug Kits — Copper
Panelboard Amps Kit Catalog Number Wire Range Crimp Tool
125 NFCUV1
#6–1/0 kcmil
13.30–53.48 mm
2
VC6-3
250 NFCUV2
(1) 2/0–300 kcmil
(1) 67.43–152 mm
2
VC6-FT,
VC7,
VC7-FT,
VC8
400 NFCUV4
(1) 400–750 kcmil
(1) 202.7–380 mm
2
600 NFCUV6
(2) 250–500 kcmil
(2) 126.7–253.4 mm
2
VC6 Series