Mars N2 Unheated Series Submittal
Table Of Contents
- N2 Unheated Submittals
- N2 Unheated Submittals Page 2
- BD14 Unhtd Sub Pkg
- PART 1 GENERAL
- 1.1 SECTION INCLUDES
- 1.2 RELATED SECTIONS
- A. Section 05 50 00 – Metal Fabrications: Concealed steel support members.
- B. Section 06 10 00 – Rough Carpentry.
- C. Section 05 41 00 – Structural Metal Studs.
- D. Section 07 62 00 – Sheet metal flashing.
- E. Section 07 92 00 – Joint Sealants.
- F. Section 08 10 00 – Metal Doors and Frames.
- G. Section 08 33 00 – Overhead Coiling Doors.
- H. Section 08 42 00 – Entrance Doors.
- I. Section 22 10 00 – Plumbing Piping:
- J. Section 23 21 00 – Hydronic Piping: Hot water heating piping to units.
- K. Section 23 22 13- Steam and Condensate Piping: Steam heating piping to units.
- L. Section 26 05 00 – Equipment Wiring: Connections to building power distribution.
- 1.3 REFERENCES
- A. ASTM A240 / A240M -10 – Standard Specification for Chromium and Chromium.
- B. ASTM A879 / A879M -06 – Standard Specification for Steel Sheet, Zinc Coated by the Electrolytic Process for Application Requiring Designation of the Coating Mass on Each Surface.
- C. ASTM A653 / A653M -09a – Standard Specification for Steel Sheet, Zinc Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
- D. UL 507 – UL Standard for Safety Electric Fans – Intertek Testing Services Listed for US and Canada.
- E. UL508A – Standard for Industrial Control Panels
- F. UL 1995/CSA 22.2 – UL Standard for Safety Heating and Cooling Equipment – Intertek Testing Services Listed for US and Canada.
- G. UL 2021/CSA 22,.2 – Standard for Fixed and Location-Dedicated Electric Room Heaters – Intertek Testing Services Listed for US and Canada.
- H. AHRI 410-2001 – Standard for Forced-Circulation Air-cooling and Air-Heating Coils.
- I. NSF/ANSI 37 – Air Curtains for entranceways in food and food service establishments – ETL Sanitation.
- J. AMCA 211 (Air Movement & Control Association International, Inc.) – Certified Ratings Program – Product Rating Manual for Fan Air Performance.
- K. CEC – Approved Elec heating Coils
- L. Electrical components UL/CUL listed.
- M. NEC – National Electric Code.
- N. U.S. Green Building Council, LEED Building Design and Construction (BD+C) Version 4.0 Rating System. (LEED v4.0).
- 1.4 SUBMITTALS
- A. Submit under provisions of Section 01 33 00.
- B. Product Data: Manufacturer's data sheets on each product to be used, including:
- C. Shop Drawings: Include plans, elevations, sections, and details, indicating dimensions, tolerances, materials, fasteners, hardware, finish, piping, electrical wiring diagrams, options, and accessories.
- D. LEED Submittals: Provide documentation of how the requirements of Credit will be met:
- 1. List of proposed materials with recycled content. Indicate post-consumer recycled content and pre-consumer recycled content for each product having recycled content.
- 2. Product data and certification letter indicating percentages by weight of post-consumer and pre-consumer recycled content for products having recycled content.
- E. Selection Samples: For each finish product specified, two complete sets of color chips representing manufacturer's full range of available colors and patterns.
- F. Verification Samples: For each finish product specified, two samples, minimum size 6.25 inches (160 mm) square, representing actual product, color, and patterns.
- G. Manufacturer's Certificates: Certify products meet or exceed specified requirements.
- H. Operation and Maintenance Manual: Submit manufacturer's operation and maintenance manual, including operation, maintenance, adjustment, and cleaning instructions, trouble shooting guide, parts list, and electrical wiring diagrams.
- 1.5 QUALITY ASSURANCE
- 1.6 DELIVERY, STORAGE, AND HANDLING
- 1.7 SEQUENCING
- A. Ensure that locating templates and other information required for installation of products of this section are furnished to affected trades in time to prevent interruption of construction progress.
- B. Coordinate the installation of wiring and control switches for air curtains with the openings and the hardware provided for such openings.
- C. Install after doors, walls, ceilings, and other adjacent surfaces are finished and painted.
- 1.8 WARRANTY
- PART 2 PRODUCTS
- 2.1 MANUFACTURER
- A. Acceptable Manufacturer: Mars Air Systems, LLC; 14716 South Broadway St., Gardena, CA 90248. Tel: (310) 532-1555 or (800) 421-1266. Fax: (310) 324-3030. Email: info@marsair.com. Web: www.marsair.com.
- B. Delete one of the following two paragraphs: coordinate with requirements of Division 1 section on product options and substitutions.
- C. Requests for substitutions will be considered in accordance with provisions of Section 01 33 00.
- 2.2 AIR CURTAIN ASSEMBLIES
- A. Motor Fan Assembly: Design for easy removal, assembly, repair, and maintenance.
- 1. Motor: Totally enclosed air over (TEAO) cooled motor with sealed lifetime pre-lubricated ball bearings, motor starter and thermal overload protection.
- a. Wired for single speed operation.
- b. Wired for two speed operation. (Not Applicable for Fly Insect Control Unit)
- c. Wired for three speed operation. (Not applicable for Fly Insect Control Unit)
- d. Provide wash down type motors, NEC IP-54 for the locations indicated.
- e. Provide explosion proof type motors, NEC Class 1, Division 1, Group D for the locations indicated.
- f. Electrical Characteristics: 115V AC, single phase; 5.1 Amp full load per motor/fan.
- g. Electrical Characteristics: 208/230V AC, single phase; 2.5 Amp full load per motor/fan.
- h. Electrical Characteristics: 208/230V AC, three-phase; 1.8/1.6 Amp full load per motor/fan.
- i. Electrical Characteristics: 460V AC, three-phase; 0.8 Amp full load per motor/fan.
- j. Electrical Characteristics: 575V AC, three-phase; 0.65 Amp full load per motor/fan.
- k. Meets NEC. ETL Listed to conform to UL 507 (US) and CSA22.2 (Canada) Standards. AMCA 211 Certified.
- 2. Fans: Forward curved centrifugal type, double width, and double inlet design, directly driven to an electric motor.
- 1. Motor: Totally enclosed air over (TEAO) cooled motor with sealed lifetime pre-lubricated ball bearings, motor starter and thermal overload protection.
- B. Housing: Self-contained one-piece type with sufficient strength for mounting from pre-punched mounting holes at both ends to adjacent walls or ceiling without intermediate support.
- 1. Size:
- a. Unheated: 12-3/4 inches deep by 10-5/8 inches high (including discharge nozzle) by width of unit.
- b. Electric Heated: 17-3/8 inches deep by 10-5/8 inches high (including discharge nozzle) by width of unit.
- c. Hot Water/Steam Heated: Depth 17-3/8 inches single row and double row by 10-5/8 inches high including discharge nozzle by width of unit plus 10 inches for manifolds.
- 2. Mounting:
- 3. Material:
- 4. Air Inlet Grille and/or Filters: Provide air inlet grille and/or filters specified.
- 5. Discharge: Provide integral discharge nozzle specified.
- 6. Finish and Color: Provide with, no VOC, corrosion resistant polyurethane powder coated finish for sheet metal housings.
- 1. Size:
- C. Environmental Air Curtains: Models for Heights to 12 feet (3656 mm) for Environmental Separation and Temperature Control and up to 10 feet (3048 mm) for Flying Insect Control (STD2 series)
- 1. Discharge Nozzle: Wedge-shaped discharge outlet nozzle with adjustable air foil vanes with a plus/minus 40-degree sweep front to back.
- 2. Air Velocity at Nozzle:
- a. STD236-1: 36 Inch (915 mm) Wide Units: 2206 feet/min (11.2 m/s) single 1/2HP motor/fan assembly.
- b. STD242-1: 42 Inch (1065 mm) Wide Units: 1945 feet/min (9.9 m/s) single 1/2HP motor/fan assembly.
- c. STD248-1: 48 Inch (1220 mm) Wide Units: 1730 feet/min (8.8 m/s) single 1/2HP motor/fan assembly.
- d. STD260-2: 60 Inch (1524 mm) Wide Units: 2592 feet/min (13.2 m/s) single 1/2HP motor/fan assembly.
- e. STD272-2: 72 Inch (1830 mm) Wide Units: 2206 feet/min (11.2 m/s) two 1/2HP motor/fan assemblies.
- f. STD284-2: 84 Inch (2133 mm) Wide Units: 1945 feet/min (9.9 m/s) two 1/2HP motor/fan assemblies.
- g. STD296-2: 96 Inch (2440 mm) Wide Units: 1730 feet/min (8.8 m/s) two 1/2HP motor/fan assemblies.
- h. STD2108-3: 108 Inch (2743 mm) Wide Units: 2206 feet/min (11.2 m/s) two 1/2HP motor/fan assemblies.
- i. STD2120-3: 120 Inch (3050 mm) Wide Units: 2084 feet/min (10.6 m/s) three 1/2HP motor/fan assemblies.
- j. STD2144-3: 144 Inch (3660 mm) Wide Units: 1730 feet/min (8.8 m/s) three 1/2HP motor/fan assemblies.
- 3. Air Speed at Floor: Minimum of 300 fpm (1.53 m/s) at 3 feet (914 mm) from the floor.
- 4. Air Inlet Grille and Filters:
- 5. Sound Pressure Level At 10 feet (3 m) From Nozzle:
- D. Insect Control Air Curtains: Models for Heights up to 7 feet (3048 mm) for Flying Insect Control. Certified to NSF/ANSI Standard 37. (N2 Series)
- 1. Discharge Nozzle: Wedge-shaped discharge outlet nozzle with adjustable air foil vanes with a plus/minus 40-degree sweep front to back.
- 2. Air Velocity at Nozzle:
- a. N236-1: 36 Inch (915 mm) Wide Units: 2206 feet/min (11.2 m/s) single 1/2HP motor/fan assembly.
- b. N242-1: 42 Inch (1065 mm) Wide Units: 1945 feet/min (9.9 m/s) single 1/2HP motor/fan assembly.
- c. N248-1: 48 Inch (1220 mm) Wide Units: 1730 feet/min (8.8 m/s) single 1/2HP motor/fan assembly.
- d. N260-2: 60 Inch (1524 mm) Wide Units: 2592 feet/min (13.2 m/s) single 1/2HP motor/fan assembly.
- e. N272-2: 72 Inch (1830 mm) Wide Units: 2206 feet/min (11.2 m/s) two 1/2HP motor/fan assemblies.
- f. N284-2: 84 Inch (1830 mm) Wide Units: 1945 feet/min (9.9 m/s) two 1/2HP motor/fan assemblies.
- g. N296-2: 96 Inch (2440 mm) Wide Units: 1730 feet/min (8.8 m/s) two 1/2HP motor/fan assemblies.
- h. N2108-3: 108 Inch (2743 mm) Wide Units: 2206 feet/min (11.2 m/s) two 1/2HP motor/fan assemblies.
- i. N2120-3: 120 Inch (3050 mm) Wide Units: 2084 feet/min (10.6 m/s) two 1/2HP motor/fan assemblies.
- j. N2144-3: 144 Inch (3600 mm) Wide Units: 1730 feet/min (8.8 m/s) two 1/2HP motor/fan assemblies.
- 3. Air Speed at Floor:
- 4. Air Inlet Grille and Filters:
- 5. Sound Pressure Level At 10 feet (3 m) From Nozzle:
- A. Motor Fan Assembly: Design for easy removal, assembly, repair, and maintenance.
- 2.3 COMPONENTS
- A. Electric Heaters: Provide complete with motor control panel factory mounted to air curtain housing, and thermostat to be field installed
- 1. Temperature limit controller.
- 2. Thermostat: Wall-mounted, 24-Volt operation, with heater on/off selection.
- 3. Heating Coils: ETL approved as part of unit. Meets NEC and CEC tested by ETL Certified to conform to UL2021(US) and CSA22.2 (Canada) Standards. Factory mounted on the discharge end of the motor fan assembly and located within the nozzle outlet.
- B. Steam Heaters: Provide finned tube steam coils for field mounting on air intake side of the air curtain cabinet with opposite end connections.
- 1. Meets NEC and CEC tested by ETL Certified to conform to UL1995(US) and CSA22.2 (Canada) Standards.
- 2. Output: Air curtain manufacturer's standard, one-row coils.
- 3. Coils: Certified in accordance with AHRI 410.
- 4. Connections: Opposite end.
- 5. Connections: Same end, right hand.
- 6. Connections: Same end, left hand.
- 7. Casing: One-piece unpainted galvanized steel, bolted to air curtain housing.
- 8. Supply and return fittings on ends of casing.
- 9. Steam Distributing coil required for 8 feet and above for same end coils. Dual supply, Single returns.
- 10. Thermostat: Wall-mounted, 110-Volt operation, with heater on/off selection.
- 11. Thermostat: Wall-mounted, 208/230-Volt operation, with heater on/off selection.
- C. Hot Water Heaters: Provide finned tube water coils for field mounting on air intake side of the air curtain cabinet with opposite end connections.
- 1. Meets NEC and CEC tested by ETL Certified to conform to UL1995(US) and CSA22.2 (Canada) Standards.
- 2. Output: Air curtain manufacturer's standard, one-row coils.
- 3. Output: Air curtain manufacturer's standard, two-row coils.
- 4. Coils: Certified in accordance with AHRI 410.
- 5. Connections: Opposite end.
- 6. Connections: Same end, right hand.
- 7. Connections: Same end, left hand.
- 8. Casing: One-piece unpainted galvanized steel, bolted to air curtain housing.
- 9. Supply and return fittings on top of casing.
- 10. Thermostat: Wall-mounted, 110-Volt operation, with heater on/off selection.
- 11. Thermostat: Wall-mounted, 208/230-Volt operation, with heater on/off selection.
- D. Motor Control Panels for Unheated Units: Recommended for all three-phase units and single phase units with combined motor capacities of more than 1 HP whenever a door limit switch is used to automatically start and stop the air curtain. Provide mot...
- 1. Mounting: Shipped loose to be field mounted.
- 2. Mounting: Factory mounted on right hand side of air curtain housing.
- 3. Mounting: Factory mounted on left hand side of air curtain housing.
- 4. Electrical components UL/CUL listed.
- 5. Panels UL 508A listed.
- 6. Optional Digital Programmable Controller:
- a. Remote Mounted High Resolution 5” Color LCD Display with Capacitive Touch technology
- b. Fully programmable controller
- c. Pre-set and fully customizable programs
- d. Time delay (Passive & Adaptive)
- e. 24/7 timer
- f. Maintenance schedule alerts
- g. Status display showing date, time, temperature, and air curtain mode
- h. Multi-unit control capability
- i. English (IP) or Metric (SI) display readings
- j. Password protected
- k. Auto Lock display
- l. Emergency shut-off button
- m. Low voltage control signal for door activation
- n. Integrated BMS controls
- o. VFD compatible with 0-10VDC output
- p. Optional BACnet option
- q. Optional adaptive fan speed control based on existing field conditions. Field mounted outdoor temperature sensors required.
- E. Motor Control Panels for Electric Heated Units: Recommended for all three-phase units and single-phase units with combined motor capacities of more than 1 HP whenever a door limit switch is used to automatically start and stop the air curtain. Moto...
- 1. Mounting: Factory mounted on the inside of air curtain housing.
- 2. Mounting: Factory mounted on left hand side of air curtain housing.
- 3. Electrical components UL/CUL listed.
- 4. Optional Digital Programmable Controller:
- a. Remote Mounted High Resolution 5” Color LCD Display with Capacitive Touch technology
- b. Fully programmable controller
- c. Pre-set and fully customizable programs
- d. Time delay (Passive & Adaptive)
- e. Factory Integrated temperature control sensors. No external thermostat required.
- f. Summer-Winter modes
- g. 24/7 timer
- h. Maintenance schedule alerts
- i. Status display showing date, time, temperature, and air curtain mode
- j. Multi-unit control capability
- k. English (IP) or Metric (SI) display readings
- l. Password protected
- m. Auto Lock display
- n. Emergency shut-off button
- o. High temperature lock from fan failure
- p. Low voltage control signal for door activation
- q. Integrated BMS controls
- r. VFD compatible with 0-10VDC output
- s. Optional BACnet option
- t. Optional adaptive fan speed control and heat control based on existing field conditions. Field mounted outdoor temperature sensors required.
- F. Motor Control Panels For Hot Water, Steam and Gas Heated Units: Recommended for all three-phase units and single phase units with combined motor capacities of more than 1HP whenever a door limit switch is used to automatically start and stop the ai...
- 1. Mounting: Shipped loose to be field mounted.
- 2. Mounting: Factory mounted on right hand side of air curtain housing.
- 3. Mounting: Factory mounted on left hand side of air curtain housing.
- 4. Provide with remote mount thermostat for field installation.
- 5. Electrical components UL/CUL listed.
- 6. Optional Digital Programmable Controller:
- a. Remote Mounted High Resolution 5” Color LCD Display with Capacitive Touch technology
- b. Fully programmable controller
- c. Pre-set and fully customizable programs
- d. Time delay (Passive & Adaptive)
- e. Factory Integrated temperature control sensors. No external thermostat required.
- f. Summer-Winter modes
- g. 24/7 timer
- h. Maintenance schedule alerts
- i. Status display showing date, time, temperature, and air curtain mode
- j. Multi-unit control capability
- k. English (IP) or Metric (SI) display readings
- l. Password protected
- m. Auto Lock display
- n. Emergency shut-off button
- o. High temperature lock from fan failure
- p. Low voltage control signal for door activation
- q. Integrated BMS controls
- r. VFD compatible with 0-10VDC output
- s. Optional BACnet option
- t. Optional adaptive fan speed control and heat control based on existing field conditions. Field mounted outdoor temperature sensors required.
- G. Door-Activated Limit switch(s): Provide, field installed 250-Volts, 20 amps limit switch to control air curtain(s) as follows; Automatic on/off control, activates air curtain when door is opened and turns off when door is closed. Provide limit swit...
- 1. Type: Combination plunger/roller switch for swing and sliding doors.
- a. Provide limit switches with NEMA 1 (20 amps) ratings in locations indicated.
- b. Provide limit switches with NEMA 4X (10 amps) ratings in locations indicated.
- c. Provide limit switches with NEMA 4X (15 amps) ratings in locations indicated.
- d. Provide limit switches with NEMA 7 (10 amps) ratings in locations indicated.
- 2. Type: Magnetic reed switch and actuator for swing and sliding doors. Industrial floor mounted or surface mounted switches for roll up doors.
- 3. Operation for Unheated Units: Automatic on/off control, on when door is opened, off when door is closed.
- 4. Operation for Heated Units: Automatic on when door is opened, off after time delay period after door is closed, maintaining heat in the event door is opened within time delay period. Field adjustable from 1 to 17 minutes.
- 1. Type: Combination plunger/roller switch for swing and sliding doors.
- H. Provide mounting hardware as required for the opening.
- A. Electric Heaters: Provide complete with motor control panel factory mounted to air curtain housing, and thermostat to be field installed
- 2.1 MANUFACTURER
- PART 3 EXECUTION
- 3.1 EXAMINATION
- A. Verify that required utilities are in correct location and are of correct capacities for specified products.
- B. Verify openings to receive air curtains are plumb, level, square, accurately aligned, correctly located, and in tolerance.
- C. Examine surfaces to receive air curtains. If surface preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.
- 3.2 INSTALLATION
- A. Install air curtains in accordance with approved shop drawings and manufacturer's printed installation instructions.
- B. Install air curtains plumb, level, square, true to line, and weathertight, without warp or rack.
- C. Anchor air curtains securely in place to supports.
- D. Coordinate with sheet metal flashing as specified in Section 07 62 00.
- E. Install joint sealants as specified in Section 07 92 00.
- F. Coordinate with electrical power as specified in Section 26 05 00.
- G. Install door limit switches and adjust for correct operation.
- H. Provide connection to piped services and utilities as specified in Section 22 10 00 and 23 21 00.
- 3.3 FIELD QUALITY CONTROL
- A. Adjust air curtains to function properly.
- B. Adjust air foil vanes located within the discharge nozzle as required for prevailing conditions at each opening.
- C. Check heated air curtain performance on a calm day by measuring air temperature 6 inches off the floor. Optimal reading is halfway between the temperature inside and outside the building.
- 3.4 CLEANING
- A. Clean air curtains promptly after installation in accordance with manufacturer's instructions.
- B. Repair minor damages to finish in accordance with manufacturer's instructions and as approved by Architect.
- C. Remove and replace damaged components that cannot be successfully repaired as determined by Architect.
- 3.5 PROTECTION
- 3.6 SCHEDULES
- 3.1 EXAMINATION
4
MAINTENANCE
Routine maintenance is required to keep this product
operating at its peak performance and efficiency. Over
time, the housing, air intake grille, air intake filter, blower
wheels and motor(s) will accumulate a buildup of dust,
debris and other residue. It is imperative to keep these
components clean. Failure to do so will not only lower
operational efficiency and performance, but also reduce
the useful life of the product. The time between cleanings
depends on the application, location, and daily hours of
use. On average, under normal use conditions, the
product should require a thorough cleaning once every
six (6) months.
To clean the product, perform the following:
1. Verify the product has been disconnected from the
power source.
2. Use a damp cloth and either a warm mild soapy water
solution or bio-degradable degreaser, to wipe down the
exterior components of the housing.
3. To access the interior of the product, remove the air
intake grille and/or air intake filter. This is accomplished
by removing the eight (8) self-tapping screws on the
face of each air intake grille/filter.
4. Thoroughly clean the air intake grille/filter.
5. Remove the motor fan assembly (MFA) from inside the
air curtain housing. This is accomplished by loosening
the watertight fitting and pulling the cord out (3 phase
power) or by the quick disconnect plug on the motor (1
phase power). Then remove the two (2) wing nuts on
the out-board sides of the MFA pan. Care should be
taken to avoid the MFA from tipping over.
6. Remove the MFA from the unit and thoroughly wipe
down the motor, blower wheels and blower wheel
housings. Be careful not to submerge the motor in water
or spray it with a water hose.
7. The motor(s) require no additional lubrication. They are
permanently lubricated and feature double sealed ball
bearings.
8. To re-install the product, reverse the procedures above.
9. Reconnect the power source to the product
10. If you have any questions regarding the maintenance of
the product, contact the manufacturer.
SPECIAL APPLICATIONS
Outdoor Installation
For outdoor unit special consideration may be required
for enclosure, motor, wheel, and other components to
minimize damage caused by exposure to the outdoor
elements. Contact factory for special construction and
costing.
Freezer and Cooler Installation
Air curtain must be mounted on the warm side for optimal
performance. Variable Frequency Drive (VFD) is strongly
recommended to control the air curtain air flow velocity at
the floor level.
High humid areas may require de-humidifier or additional
defrost cycle to minimize condensation and freezing for
freezer applications. We recommend the air curtain unit
to not replace doors but work in conjunction with door
opening sequence cycle. Contact factory for details.
a control panel or an On/Off switch, open the door
to energize the product.
J. If heated products are installed, reference Heated
Products Supplement.
K. For three phase units, verify direction of rotation of
blower wheels (note direction arrows on the blower
wheel housing). Correct if needed by changing
polarity of three phase power.
L. VERY IMPORTANT Using a clamp meter, measure
the amperage to each motor and ensure that they
do not exceed the amperage listed on the product
label.
M. If applicable, adjust the air intake grille(s) such that
the output air stream reaches the floor. For
temperature control and environmental separation
applications, the air stream should reach the floor
with sufficient strength to create an air seal around
the door opening without creating turbulent mixing
of the inside and outside air. For flying insect
control applications, the air stream should reach the
floor with maximum strength. If after proper
installation and adjustment, the product appears to
be producing too little or too much air for the
application, contact the manufacturer.
WARNING
Prevent hazard of electrical shock. More than one
disconnect switch may be required to de-energize this
product.
WARNING
To reduce the risk of fire, electrical shock, or injury to
persons, observe the following:
A. Maintenance is to be performed only by qualified
personnel who are familiar with local codes and
regulations and are experienced with this type of
product.
B. Before servicing or cleaning the product switch power
off at service panel and lock service panel to prevent
power from being switched “ON” accidentally.