Product manual

9
ComPac 6/09-18
1.5 General Operation
Refrigerant Cycle (Cooling Mode)
The ComPac
®
I & ComPac
®
II A/C use R-22 refrigerant in a conventional vapor-compression refrigera-
tion cycle to transfer heat from air in an enclosed space to the outside. A double blower assembly blows
indoor air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled into gas
by heat removed from the air. The warmed refrigerant gas enters the compressor where its temperature
and pressure are increased. The hot refrigerant gas condenses to liquid as heat is transferred to outdoor
air drawn across the condenser by the condenser fan. Liquid refrigerant is metered into the evaporator
through capillary tubes to repeat the cycle.
Heating Mode
A wall-mounted thermostat controls the heating cycle of models which incorporate resistance heating
elements. On a call for heat, the thermostat closes the heat relay to energize the indoor fan and the
resistance elements. Except on units with the optional dehumidication kit, the compressor is locked
out during the heating cycle.
Economizer Operation (ComPac
®
II A/C Only)
The economizer is a regulated damper system with controls. The damper regulates the circulation
of outside air into the enclosure (when the outdoor air conditions are suitable) to reduce the need for
mechanical cooling, save energy, and extend compressor life.
Depending upon the options selected, the damper responds to the enthalpy of the outdoor air. On a call
for cooling from a space thermostat, it operates as follows:
When the enthalpy of the outdoor air is below the set point, the outdoor air damper is proportion-
ally open (and return air damper is proportionally closed) to maintain between 50°F and 56°F at the
mixed/discharge air sensor. Integral pressure relief allows the indoor air to exit the shelter through the
air conditioner.
When the enthalpy of the outdoor air is above the set point, the outdoor air damper closes to its minimum
position. A call for cooling from the space thermostat brings on mechanical cooling.
An optional built-in adjustable minimum position potentiometer (part number 70012) controls the
amount of outdoor air admitted to meet minimum ventilation requirements.
Figure 2. Refrigerant Circuit
Evaporator (Indoor Coil)
Distributor &
Capillary
Tubes
Filter
Drier
Twin Blowers
Discharge Line
Condenser Fan
Condenser (Outdoor Coil)
Suction
Line
Compressor