Specifications

15
ModPac II, 9/09-15
Figure 5. Wall Mounting Detail - Models AVP24-60
2.8 Mounting the Unit
1. For wiring into the back of unit, locate the lower of the two knock-outs on the wall side of
the ModPac II™ A/C. Drill a one inch hole in the shelter wall to match this opening. Allow
sufcient clearance to run 3/4" conduit through the hole and to the unit.
2. Apply a generous bead of silicone sealer on the wall side of the mounting brackets on the
ModPac II™ A/C. Circle the mounting holes with the silicone bead.
3.
Using an appropriate and safe lifting device, set the ModPac II™ A/C on the bottom sup-
port bracket mounted on the wall. You must stabilize the unit on the bracket with the lifting
device or by some other means - the bracket alone is not sufcient.
4. Make sure that the duct anges are properly aligned with the wall opening. Adjust as neces
-
sary.
5. Note the holes in each side bracket. Using the holes for guides, drill holes through the wall
with a 3/8" drill bit. Insert the 3/8 x 5" bolts through the brackets. Install nuts and washers
on the inside of the building. Tighten the bolts to secure the unit.
For units with electric heat, a one inch clearance is required around the
duct extensions. The duct extensions must be constructed of galvanized
steel with a minimum thickness of .019” as per the NFPA standards 90A
& 90B.