State of Florida Department of Transportation VETERANS EXPRESSWAY (SR 589) AET PHASE 6B SUGARWOOD PLAZA SB & NB RAMPS at GUNN HIGHWAY SB & NB RAMPS at HUTCHISON ROAD FPID: 406151-4-52-01 HILLSBOROUGH COUNTY, FLORIDA Gantry Equipment Building HVAC Calculations and Cut Sheets Submitted by: January 15, 2013
INDEX Building “U” Value Calculations 1 Design Conditions 1 Gantry Building Internal heat Loads 1-2 Sugarwood Cooling Load Calculation Output & Input Data 3-7 Gunn Highway Cooling Load Calculation Output & Input Data 8 - 12 Hutchison Road Cooling Load Calculation Output & Input Data 13 – 17 Gantry Equip. Build. FL Energy Eff. Compliance Form 506-2012 18 – 24 Gantry Equip. Build. FL Energy Eff.
BUILDING “U” VALUES WALLS Outside Film 4” concrete 2” Rigid Insulation ¾” Plywood Inside Film R 0.17 3.33 5.00 0.93 0.68 10.11 “U” Walls = 0.0989 ROOF Outside Air Film Roofing Membrane 5” Rigid Insulation 4” concrete Inside Air Film R 0.17 0.34 19.0 3.33 0.68 23.52 “U” Roof = 0.0425 DESIGN CONDITIONS Location: Tampa, FL ASHRAE 2009 Fundamentals, 0.4% Annual Cooling Design Conditions Outdoor Indoor SUMMER Dry Bulb Wet Bulb 92.5° F 77.5° F 75° F 62.
Gunn Highway Entry and Exit Gantry Equipment Buildings: 1 – 16 KVA UPS 1 – Toll Equipment Rack 1 – Communication Cabinet 1 – “C” Panel 1 – ATS 1 – SCADA Panel Lights 1.7 Watts / Square Foot 6,000 BTU/HR 2,500 Watts 2,500 Watts 150 Watts 150 Watts 300 Watts 390 Watts Hutchison Road Entry and Exit Gantry Equipment Buildings: 1 – 16 KVA UPS 1 – Toll Equipment Rack 1 – Communication Cabinet 1 – “C” Panel 1 – ATS 1 – SCADA Panel Lights 1.
3 Veterans Expressway Tampa, Florida 28.0 deg 82.0 deg 5 19 ft in. Hg 29.9 0.0760 0.2444 1.1147 4,906.9 4.5604 93 78 40 0.90 0.95 0.20 0.
4 56,612 100.00 56,612 57.1 0.0 0.0 2,437 0 0 75.0 0.0 0.0 56.3 0.0 0.0 0 0 0 0 1,334 0 52,103 53,437 0 0 632 0 55 2,488 0 0 0 0 3,175 37.7 0.0 0.0 Sens Cap. Coil Airflow Enter DB/WB/HR MBh cfm °F °F gr/lb Veterans Expressway VETS XPRSWY SUGARWD GANTRY.TRC 57.1 4.8 Total Project Name: Dataset Name: 57.1 0.0 0.0 4.8 0.0 0.
Floor Multiplier: 1 Room Multiplier: 1 Project Name: Veterans Expressway Dataset Name: T:\Toll Gantry\AET 6B & 6C\Mech_MJO\AET 6B\~Calcs\Load Calcs\Sugarwood\VETS 20 Area ft² 0 0.00 0.20 System Description: AC-1 None 0.00 Adj Temp/ Grnd Refl 100 100 100 100 100 100 Pct Sen/ Cool Tmp 100 100 100 100 100 100 0 60.00 0 60.00 0 60.00 0 60.00 0 60.00 0 60.00 Pct Pct Rad Rm/ Ret/ Frc/ Heat Perm Loss Tmp Len Coef To be calculated To be calculated TRACE® 700 v6.2.
= 3 hours Veterans Expressway VETS XPRSWY SUGARWD GANTRY.TRC 0.213 Btu/hr·ft²·°F 0.20 Btu/lb·°F 0.20 Btu/lb·°F Specific Heat U-Value = 0.388 Btu/hr·ft²·°F C-Coefficient = 0.2400 Btu/hr·ft²·°F 100.00 lb/cu ft 100.00 lb/cu ft Density 0.20 Btu/lb·°F Specific Heat U-Value = 0.041 Btu/hr·ft²·°F C-Coefficient = 0.0100 Btu/hr·ft²·°F 40.00 lb/cu ft Density Roof - Construction Types 0.10 Btu/hr·ft·°F Conductivity 13.33 lb/ft² 2.67 Btu/ft²·lb·°F 4.00 in. Weight = Heat Capacity = 4 in.
Description Thickness 1.00 0% SUSFLUOR Veterans Expressway VETS XPRSWY SUGARWD GANTRY.TRC Ballast Factor Percent Lights to RA Fixture Type Fluorescent, hung below ceiling, 100% load to space 0.00 Solar Transmissivity 67 % 0% Longwave Radiant Fraction Shortwave Radiant Fraction Lights 0.50 Inside Visible Reflectivity 0.20 Btu/hr·ft²·°F 0.00 Glass U-Value 0.00 Visible Transmissivity Shading Coeff Number of Panes 1 0.69 Solar Transmissivity 0.95 Glass U-Value Alpha = 0.
8 Veterans Expressway Tampa, Florida 28.0 deg 82.0 deg 5 19 ft in. Hg 29.9 0.0760 0.2444 1.1147 4,906.9 4.5604 93 78 40 0.90 0.95 0.20 0.
9 29,622 100.00 29,622 29.9 0.0 0.0 1,329 0 0 75.0 0.0 0.0 56.9 0.0 0.0 0 0 0 0 1,334 0 25,113 26,447 0 0 632 0 55 2,488 0 0 0 0 3,175 40.2 0.0 0.0 Sens Cap. Coil Airflow Enter DB/WB/HR MBh cfm °F °F gr/lb Veterans Expressway VETS XPRSWY GUNN HWY GANTRY.TRC 29.9 2.5 Total Project Name: Dataset Name: 29.9 0.0 0.0 2.5 0.0 0.
Floor Multiplier: 1 Room Multiplier: 1 Project Name: Veterans Expressway Dataset Name: T:\TOLL GANTRY\AET 6B & 6C\MECH_MJO\AET 6B\~CALCS\LOAD CALCS\GUNN 20 Area ft² 0 0.00 0.20 System Description: AC-1 None 0.00 Adj Temp/ Grnd Refl 100 100 100 100 100 100 Pct Sen/ Cool Tmp 100 100 100 100 100 100 0 60.00 0 60.00 0 60.00 0 60.00 0 60.00 0 60.00 Pct Pct Rad Rm/ Ret/ Frc/ Heat Perm Loss Tmp Len Coef To be calculated To be calculated TRACE® 700 v6.2.
= 3 hours Veterans Expressway VETS XPRSWY GUNN HWY GANTRY.TRC 0.213 Btu/hr·ft²·°F 0.20 Btu/lb·°F 0.20 Btu/lb·°F Specific Heat U-Value = 0.388 Btu/hr·ft²·°F C-Coefficient = 0.2400 Btu/hr·ft²·°F 100.00 lb/cu ft 100.00 lb/cu ft Density 0.20 Btu/lb·°F Specific Heat U-Value = 0.041 Btu/hr·ft²·°F C-Coefficient = 0.0100 Btu/hr·ft²·°F 40.00 lb/cu ft Density Roof - Construction Types 0.10 Btu/hr·ft·°F Conductivity 13.33 lb/ft² 2.67 Btu/ft²·lb·°F 4.00 in. Weight = Heat Capacity = 4 in.
Description Thickness 1.00 0% SUSFLUOR Veterans Expressway VETS XPRSWY GUNN HWY GANTRY.TRC Ballast Factor Percent Lights to RA Fixture Type Fluorescent, hung below ceiling, 100% load to space 0.00 Solar Transmissivity 67 % 0% Longwave Radiant Fraction Shortwave Radiant Fraction Lights 0.50 Inside Visible Reflectivity 0.20 Btu/hr·ft²·°F 0.00 Glass U-Value 0.00 Visible Transmissivity Shading Coeff Number of Panes 1 0.69 Solar Transmissivity 0.95 Glass U-Value Alpha = 0.
13 Veterans Expressway Tampa, Florida 28.0 deg 82.0 deg 5 19 ft in. Hg 29.9 0.0760 0.2444 1.1147 4,906.9 4.5604 93 78 40 0.90 0.95 0.20 0.
14 29,622 100.00 29,622 29.9 0.0 0.0 1,329 0 0 75.0 0.0 0.0 56.9 0.0 0.0 0 0 0 0 1,334 0 25,113 26,447 0 0 632 0 55 2,488 0 0 0 0 3,175 40.2 0.0 0.0 Sens Cap. Coil Airflow Enter DB/WB/HR MBh cfm °F °F gr/lb Veterans Expressway VETS XPRSWY HUTCH GANTRY.TRC 29.9 2.5 Total Project Name: Dataset Name: 29.9 0.0 0.0 2.5 0.0 0.
Floor Multiplier: 1 Room Multiplier: 1 Project Name: Veterans Expressway Dataset Name: T:\TOLL GANTRY\AET 6B & 6C\MECH_MJO\AET 6B\~CALCS\LOAD 20 Area ft² 0 0.00 0.20 System Description: AC-1 None 0.00 Adj Temp/ Grnd Refl 100 100 100 100 100 100 Pct Sen/ Cool Tmp 100 100 100 100 100 100 0 60.00 0 60.00 0 60.00 0 60.00 0 60.00 0 60.00 Pct Pct Rad Rm/ Ret/ Frc/ Heat Perm Loss Tmp Len Coef To be calculated To be calculated TRACE® 700 v6.2.
= 3 hours Veterans Expressway VETS XPRSWY HUTCH GANTRY.TRC 0.213 Btu/hr·ft²·°F 0.20 Btu/lb·°F 0.20 Btu/lb·°F Specific Heat U-Value = 0.388 Btu/hr·ft²·°F C-Coefficient = 0.2400 Btu/hr·ft²·°F 100.00 lb/cu ft 100.00 lb/cu ft Density 0.20 Btu/lb·°F Specific Heat U-Value = 0.041 Btu/hr·ft²·°F C-Coefficient = 0.0100 Btu/hr·ft²·°F 40.00 lb/cu ft Density Roof - Construction Types 0.10 Btu/hr·ft·°F Conductivity 13.33 lb/ft² 2.67 Btu/ft²·lb·°F 4.00 in. Weight = Heat Capacity = 4 in.
Description Thickness 1.00 0% SUSFLUOR Veterans Expressway VETS XPRSWY HUTCH GANTRY.TRC Ballast Factor Percent Lights to RA Fixture Type Fluorescent, hung below ceiling, 100% load to space 0.00 Solar Transmissivity 67 % 0% Longwave Radiant Fraction Shortwave Radiant Fraction Lights 0.50 Inside Visible Reflectivity 0.20 Btu/hr·ft²·°F 0.00 Glass U-Value 0.00 Visible Transmissivity Shading Coeff Number of Panes 1 0.69 Solar Transmissivity 0.95 Glass U-Value Alpha = 0.
Florida Energy Efficiency Code For Building Construction EnergyGauge Summit® Fla/Com-2010, Effective Date: March 15, 2012 -- Form 506-2010 Total Building Performance Method for Commercial Buildings PROJECT SUMMARY Short Desc: Ganrty Eq Bldg Description: AET 6B Gantry Equip Build.
Compliance Summary Component Design Gross Energy Cost (in $) 138.0 Criteria 389.0 Result PASSED LIGHTING CONTROLS PASSES EXTERNAL LIGHTING PASSES HVAC SYSTEM PASSES PLANT None Entered WATER HEATING SYSTEMS None Entered PIPING SYSTEMS None Entered Met all required compliance from Check List? Yes/No/NA IMPORTANT MESSAGE Info 5009 -- -- -- An input report of this design building must be submitted along with this Compliance Report EnergyGauge Summit® Fla/Com-2010. Section 506.
CERTIFICATIONS I hereby certify that the plans and specifications covered by this calculation are in compliance with the Florida Energy Code Prepared By: Michael J.
Project: Ganrty Eq Bldg Title: AET 6B Gantry Equip Build. Type: Transportation (WEA File: FL_TAMPA_INTERNATIONAL_AP.tm3) Building End Uses 1) Proposed 2) Baseline 8.80 30.60 $138 $486 8.80 2563 30.60 8944 $138 $486 4.00 1176 3.60 1057 $63 $57 0.50 135 0.50 135 $7 $7 2.80 806 6.80 1990 $43 $108 0.00 0 3.10 902 $0 $49 1.50 446 16.
Project: Ganrty Eq Bldg Title: AET 6B Gantry Equip Build. Type: Transportation (WEA File: FL_TAMPA_INTERNATIONAL_AP.tm3) External Lighting Compliance Description Category Tradable? Ext Light 1 Building facades (by linear foot) Allowance (W/Unit) No Area or Length ELPA or No. of Units (W) (Sqft or ft) 5.00 67.0 CLP (W) 335 128 PASSES Tradable Surfaces: 0 (W) Allowance for Tradable: 750 (W) All External Lighting: 128 (W) Complicance check includes a excess/Base allowance of 750.
Plant Compliance Description Installed No Size Design Eff Min Eff Design IPLV Min IPLV Comp liance Category None Water Heater Compliance Description Type Category Design Eff Min Eff Design Loss Max Loss Comp liance None Piping System Compliance Category Pipe Dia [inches] Is Runout? Operating Ins Cond Temp [Btu-in/hr [F] .SF.F] Ins Thick [in] Req Ins Compliance Thick [in] None EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software.
Project: Ganrty Eq Bldg Title: AET 6B Gantry Equip Build. Type: Transportation (WEA File: FL_TAMPA_INTERNATIONAL_AP.tm3) Other Required Compliance Category Section Requirement (write N/A in box if not applicable) Check Report 506.4.2 Input Report Print-Out from EnergyGauge FlaCom attached X Operations Manual Operations manual provided to owner X Windows & Doors 303.3.1, 503.2.9.3, 505.7.4.2 502.3.2 X Joints/Cracks 502.3.3 Glazed swinging entrance & revolving doors: max. 1.
25 Eq Bldg 1 No Acronym Acronym No 10/2/2012 Ganrty Eq Bldg Description Ganrty Equipment Bldg Type Depth [ft] Spaces Building Type: Orientation: Width [ft] Height [ft] 230.0 Area [sf] Total Area [sf] 1 Multiplier 230 1 Total Volume [cf] 230.0 Total Area [sf] SF New Finished building Transportation North Multi plier GrossArea: No.of Stories: Building Classification: EnergyGauge Summit® v4.
26 Type Description West Wall 4 10/2/2012 In Zone: In Wall: East Wall 3 No South Wall 2 Description In Zone: Eq Bldg 1 North Wall No Type Walls 6 No. of Luminaires Lighting 20.00 1 1 1 1 U [Btu/hr sf F] 384 Power [W] 9.50 1 H (Effec) [ft] W 0.1065 0.1065 0.1065 0.1065 Multi plier 9.959 9.959 9.959 9.959 Heat Capacity [Btu/sf.F] Manual On/Off [ft] West East South North 230.0 Control Type Direction Conductance [Btu/hr. sf. F] 64 Vis.Tra 210.0 210.0 125.
27 1 No 1 Eq Bldg Floor Type Aluminum door, 1.25 in. polystyrene Type 1 ft soil, concrete floor, vinyl tile Type Type Gantry Equip Bldg Roof Description Description No Description Eq Bldg Roof No 10/2/2012 In Zone: Description Eq Bldg In Wall: North 1 North Wall Door In Zone: In Roof: In Zone: In Zone: No 1 H (Effec) Multi [ft] plier 32.00 262.5 Area [sf] 1 0.4219 10.75 29.33 110.00 Heat Cap. Dens. [Btu/sf. F] [lb/cf] [ft] 0.53 [Sf] Total Area 28.7 R-Value [h.sf.
28 No 10/2/2012 1 Type Ext Light 1 Description W-Heater Description Category Capacity Cap.Unit 1900.00 56000.00 Capacity Piping 4 No. of Luminaires 32 EnergyGauge Summit® v4.10 Insulation Conductivity [ Btu-in/h.sf.F] Watts per Luminaire Ext-Lighting I/P Rt. Water Heaters Size Eff. IPLV Control Type Loss Insulation Thickness [in] Is Runout? 128.00 [W] Wattage IPLV No. Of Units 1 Photo Sensor control Nomonal pipe Diameter [in] 67.00 [sf/ft/No] Area/Len/No.
29 Matl151 Matl265 Matl159 Matl94 Matl407 Matl414 ApLbMat1002 ApLbMat1004 151 265 159 94 407 414 1002 1004 10/2/2012 Name Matl214 214 No Matl264 PLYWOOD, 3/4IN LINOLEUM TILE R-8 generic Insulatrion CONC HW-UNDRD-140LB-4IN BUILT-UP ROOFING, 3/8IN R-19 Generic Insulation 0.9470 0.0500 8.0000 19.0000 0.3366 0.3202 2.0000 0.4403 5.2100 0.0002 RValue [h.sf.F/Btu] Massless Construct 0.0625 0.1746 0.4147 0.0313 0.3333 1.0000 0.3333 0.1042 0.
30 264 3 10/2/2012 Material No. 151 414 1004 Layer 1 2 3 Gantry Equip Bldg Wall 1002 3 1062 159 2 Name 265 1 No Material No. Layer 1 ft soil, concrete floor, vinyl tile 214 2 1061 264 1 Name Material No. Layer No No Simple Construct No Simple Construct PLYWOOD, 3/4IN R-8 generic Insulatrion No Massless Construct No Massless Construct No 0.0625 0.1746 0.3333 0.42 0.11 Conductance [Btu/h.sf.F] Thickness [ft] 0.3333 1.0000 0.19 Conductance [Btu/h.sf.
31 10/2/2012 Material No. 94 407 151 414 1004 1 2 3 4 5 Gantry Equip Bldg Roof 1063 Layer Name No PLYWOOD, 3/4IN R-8 generic Insulatrion No Massless Construct 0.0625 0.1746 0.3333 0.4147 0.0313 Thickness [ft] 0.03 Conductance [Btu/h.sf.F] EnergyGauge Summit® v4.10 CONC HW, DRD, 140LB, 4IN R-19 Generic Insulation BUILT-UP ROOFING, 3/8IN Material No Simple Construct 0.000 0.000 0.000 0.000 0.000 Framing Factor 10.75 Heat Capacity [Btu/sf.F] 50.33 Density [lb/cf] 28.
ComPac® I & ComPac® II 2 to 6 Ton Vertical Wall Mount Air Conditioners Models AVPA24-30-36-42-48-60-72 (Single Stage Compressor) Models HVEA24-30-36-42-49-60 (Single Stage Compressor) Models HVESA36-42-49-60 (2-Stage Compressor) General Description The Marvair® ComPac® I and ComPac® II air conditioners are used primarily to cool electronic and communication equipment shelters. Due to the high internal heat load, these shelters require cooling even when outside temperatures drop below 60°F (15°C).
Standard Features Designed for Operation in Low Ambient Conditions • Low ambient control cycles condenser fan to maintain proper refrigerant pressures. Allows operation in mechanical cooling (compressor) down to 0ºF (-18ºC). Note: low temperature operation is affected by ambient conditions, e.g. wind and humidity. • Three minute by-pass of the low pressure switch for startup of compressor when outdoor temperatures are below 55°F (13°C). • Factory built-in economizer.
Controllers and Thermostats Controllers CommStat 4 Telecom HVAC Controller P/N S/7846 The CommStat 4 HVAC controller is designed specifically for controlling two redundant air conditioners, heat pumps or air conditioners with 2-stage compressors in a telecommunication shelter. The CommStat 4 has seven outputs for remote alarms or notification. Status LED’s indicate HEAT, COOL, POWER and the LEAD unit. When a fault is detected, an alarm LED flashes and the LCD screen displays the fault.
Model Identification •VP S A • AC • A = Air Source Vertical Package H = High Efficiency Vertical Package • • Special Option Code R = Electric Reheat U = Scroll Comp. Power Supply A = 208/230V,1ø,60Hz C = 208.
Certified Efficiency and Capacity Ratings at ANSI/AHRI Standard 390 for HVESA Air Conditioners with 2-Stage Compressors HVESA36 HVESA42 HVESA49 HVESA60 Model Number ACA Cooling BTUH1 - 2nd Stage ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC 35,000 39,000 47,000 56,000 EER2 - 2nd Stage 11.00 10.50 11.75 10.50 Integrated Part Load Value3 16.0 14.1 16.0 14.8 Rated Air Flow (CFM4) 1,300 1,400 1,750 1,900 ESP5 @ Rated Conditions 0.15 0.15 0.20 0.
Electrical Characteristics - Compressor, Fan & Blower Motors HVESA Air Conditioner with 2-Stage Compressor BASIC MODEL COMPRESSOR INDOOR FAN MOTOR (ECM6) OUTDOOR FAN MOTOR Type VOLTS-HZ-PH RLA 1 LRA 2 VOLTS-HZ-PH RPM 3 4 FLA HP 5 RPM3 VOLTS-HZ-PH FLA4 HP5 HVESA36ACA 208/230-60-1 16.6 82.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2 HVESA42ACA 208/230-60-1 16.6 96.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2 SCROLL HVESA49ACA 208/230-60-1 21.
Dimensional Data - AVPA72, and HVEA49/60, HVESA49/60 ComPac® I & ComPac® II Air Conditioners 7-9/16" 192 mm 29-3/4" 756 mm 7-9/16" 192 mm 44-7/8" 1140 mm 43-1/8" 1095 mm 1-5/16" 33 mm 1-3/4" 45 mm Supply Air 30" x 10" (Nominal) 762 mm x 254 mm 17-1/2" 445 mm 3/8" (10 mm) Diameter Mounting Holes 30-1/4" 768 mm 2-11/16" 68 mm 17-1/2" 445 mm 2-11/16" 68 mm Return Air 30" x 16" (Nominal) 762 mm x 406 mm 2" (51 mm) 2" (51 mm) 94-5/16" 2395 mm 93-1/16" 2364 mm Pull Disconnect Access Door 17-1/2" 4
ComPac® I & ComPac® II 2 to 6 Ton Vertical Wall Mount Air Conditioners Models AVPA24-30-36-42-48-60-72 (Single Stage Compressor) Models HVEA24-30-36-42-49-60 (Single Stage Compressor) Models HVESA36-42-49-60 (2-Stage Compressor) General Description The Marvair® ComPac® I and ComPac® II air conditioners are used primarily to cool electronic and communication equipment shelters. Due to the high internal heat load, these shelters require cooling even when outside temperatures drop below 60°F (15°C).
Standard Features Designed for Operation in Low Ambient Conditions • Low ambient control cycles condenser fan to maintain proper refrigerant pressures. Allows operation in mechanical cooling (compressor) down to 0ºF (-18ºC). Note: low temperature operation is affected by ambient conditions, e.g. wind and humidity. • Three minute by-pass of the low pressure switch for startup of compressor when outdoor temperatures are below 55°F (13°C). • Factory built-in economizer.
Controllers and Thermostats Controllers CommStat 4 Telecom HVAC Controller P/N S/7846 The CommStat 4 HVAC controller is designed specifically for controlling two redundant air conditioners, heat pumps or air conditioners with 2-stage compressors in a telecommunication shelter. The CommStat 4 has seven outputs for remote alarms or notification. Status LED’s indicate HEAT, COOL, POWER and the LEAD unit. When a fault is detected, an alarm LED flashes and the LCD screen displays the fault.
Model Identification •VP S A • AC • A = Air Source Vertical Package H = High Efficiency Vertical Package • • Special Option Code R = Electric Reheat U = Scroll Comp. Power Supply A = 208/230V,1ø,60Hz C = 208.
Certified Efficiency and Capacity Ratings at ANSI/AHRI Standard 390 for HVESA Air Conditioners with 2-Stage Compressors HVESA36 HVESA42 HVESA49 HVESA60 Model Number ACA Cooling BTUH1 - 2nd Stage ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC 35,000 39,000 47,000 56,000 EER2 - 2nd Stage 11.00 10.50 11.75 10.50 Integrated Part Load Value3 16.0 14.1 16.0 14.8 Rated Air Flow (CFM4) 1,300 1,400 1,750 1,900 ESP5 @ Rated Conditions 0.15 0.15 0.20 0.
Electrical Characteristics - Compressor, Fan & Blower Motors HVESA Air Conditioner with 2-Stage Compressor BASIC MODEL COMPRESSOR INDOOR FAN MOTOR (ECM6) OUTDOOR FAN MOTOR Type VOLTS-HZ-PH RLA 1 LRA 2 VOLTS-HZ-PH RPM 3 4 FLA HP 5 RPM3 VOLTS-HZ-PH FLA4 HP5 HVESA36ACA 208/230-60-1 16.6 82.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2 HVESA42ACA 208/230-60-1 16.6 96.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2 SCROLL HVESA49ACA 208/230-60-1 21.
17 B C D 117 mm E 38 mm 57 mm F R.H.
CommStat 4™ Controller CommStat 4™ Telecom HVAC Controller The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners, heat pumps and air conditioners with two stage compressors in a telecommunications shelter or enclosure. In addition to the control of the air conditioners or heat pumps, the CommStat 4 has seven outputs for remote alarms or notification. The CommStat 4 uses RS-485 communications via a RJ11 communication jack.
Specification/Features there is no longer an input from the smoke detector. All alarms are functional when 24 VAC is applied to the board. If 24 VAC is not present, no alarms will be displayed unless DC power is present. If DC power is supplied to the board, the display is operational. Thermostat • Cooling Set Point: 65°F through 95°F (18°C through 35°C) in 1° increments. • Heating Set Point: 50°F through 80°F (10°C through 27°C) in 1° increments.
CommStat 4 Lead/Lag Controller Inputs 1. Input Power The R and C terminals are the input power terminals for each respective air conditioner or heat pump. 2. Modem Connection The modem connection is used for remote communication and remote programming of the CommStat 4. It has the capability of providing shelter temperatures, mode of operation, as well as remote diagnosis. All configuration settings can be viewed and changed remotely. 3.
CommStat 4 Lead/Lag Controller Inputs (cont'd) 10. Lockout Relay (LOR) The CommStat 4 has a lockout relay input (LOR) and will provide a Normally Open (NO) or Normally Closed (NC) output in accordance to this input. This feature is enabled in the Configuration Mode, screen #10 by either selecting On (default) or Off. If On is selected, the control will turn the output off, energize the lockout relay output (NO or NC), and annunciate which unit is locked out on the LCD display.
CommStat 4 Lead/Lag Controller Outputs (cont'd) blower will be energized with a DC inverter (if an inverter is present). There is a 2°F (1°C) differential for this alarm to reset. The temperature for the second stage high temperature alarm can be selected in screen #7 of the Configuration Menu. 11. Smoke alarm The smoke alarm is energized when the smoke detector inputs sense a smoke fault condition. All outputs are off and the smoke alarm relay is energized during a smoke fault.
Thermostat and Line Voltage Connections Schematic Dimensional Data 7 CommStat 4 PDS 8.
Alarm Connections Schematic 230 VAC UNIT 1 230 VAC UNIT 2 TM UNIT 1 * DC AMR R C Y 2 W G O/Y2 MAR LOR LOR NO COM NC UNIT 2 DOWN Mode UP UNIT 1 LEAD Off/On Comfort HEAT SMOKE IN COOL AUX 1 IN AUX 2 IN POWER Alarm Lockout THERM 3 THERM 2 THERM 1 SMOKE NC COM NO NO COM NC HIGH VOLTAGE NC COM NO HIGH VOLTAGE NC COM NO HIGH VOLTAGE NC COM NO LOCKOUT NO COM NC AUX 1 Jacks for connection to second Commstat 4 or for remote communication Alarm Outputs NO COM NC AUX 2 LOW VOLTAG
® 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761-7476 • FAX (816) 765-8955 ELC6375DXD DRAINABLE COMBINATION LOUVER MIAMI-DADE APPROVED MIAMI-DADE COUNTY, FLORIDA NOTICE OF ACCEPTANCE NUMBER: 08.1211.05 (Expires 2/11/14) Florida Product Approval #FL12232.1 STANDARD CONSTRUCTION FEATURES FRAME 6" (152) deep, 6063T5 extruded aluminum with .125" (3.2) nominal wall thickness. Downspouts and caulking surfaces provided. BLADES Front stationary drainable blades – 6063T5 extruded aluminum with .
MIAMI-DADE COUNTY HURRICANE STRUCTURAL TEST PERFORMANCE SIZES TESTED: 165”w x 753/4"h (4391 x 1924) and 165”w x 120"h (4191 x 3048) TAS 201-94 LARGE MISSILE IMPACT TEST MISSILE TYPE 9 lb (4kg) Southern Pine 2" x 4" (51 x 102) VELOCITY IN FT/SEC (M/SEC) 50 (15.24) IMPACTS 6 TAS 202-94 UNIFORM STATIC AIR PRESSURE TEST (LOUVER ONLY) LOAD IN PSF (kPA) +82.5 (+3.9) -82.5 (-3.9) +110.0 (+5.3) -110.0 (-5.3) +165.0 (+7.9) -165.0 (-7.
FREE AREA GUIDE Free Area Guide shows free area in ft2 and m2 for various sizes of ELC6375DXD. Width – Inches (Meters) Height – Inches (Meters) 12 0.30 18 0.46 24 0.61 30 0.76 36 0.91 42 1.07 48 1.22 54 1.37 60 1.52 66 1.68 72 1.83 78 1.98 84 2.13 90 2.29 96 2.44 102 2.59 108 2.74 114 2.90 120 3.05 12 0.30 18 0.46 24 0.61 30 0.76 36 0.91 42 1.07 48 1.22 55 1.40 0.25 0.02 0.48 0.04 0.69 0.06 0.93 0.09 1.16 0.11 1.39 0.13 1.63 0.15 1.86 0.17 2.09 0.19 2.33 0.22 2.56 0.24 2.79 0.26 3.03 0.28 3.26 0.
MULTI SECTION ASSEMBLY FIELD SPLICE DETAIL 1/4" - 20 x 21/2" long HHB with nut & lockwasher 18” c-c & 6” from top & bottom. B” 1 Sealant (by others) A” x B” 1.