Specifications
Library Members
Wall - Construction Types
4" HW Concrete, R-5 Ins
4" heavyweight concrete block, 1" insulation
Conductivity Density ResistanceDescription Thickness Specific HeatLayer Code
0.17 ft²·hr·°F/Btu
1 M146
Outside Surface Resist. 15 m
0.10 40.00Btu/hr·ft·°F lb/cu ft 0.20 Btu/lb·°F 2 C1 4 in. LW Concrete in.4.00
5.00 ft²·hr·°F/Btu
3 M180
2" Insulation, R-5
0.07 34.00Btu/hr·ft·°F lb/cu ft 0.29 Btu/lb·°F 4 M58
3/4 in. Plywood Sheathing
0.75 in.
0.69 ft²·hr·°F/Btu 5 E0 Inside Surface Resist.
=0.90Alpha= 0.099U-Value Btu/hr·ft²·°Flb/ft²Lamda = 0.78 Weight = 15.46
C-Coefficient = 0.0200 Btu/hr·ft²·°FBtu/ft²·lb·°F=Delta hours4
Heat Capacity
=3.28
Glass types
Single Clear 1/4"
Properties based on Std DS Glass
0.95
0.95
Btu/hr·ft²·°F
Shading Coeff
Glass U-Value
1Number of Panes 0.78Visible Transmissivity
0.14Inside Visible Reflectivity
0.69Solar Transmissivity
0.13
0.84
0.84
Inside Solar Reflectivity
Outside Long Wave Emissivity
Inside Long Wave Emissivity
Standard Door
Properties based on Spectral Data
0.20
0.00
Btu/hr·ft²·°F
Shading Coeff
Glass U-Value
1Number of Panes 0.00Visible Transmissivity
0.50Inside Visible Reflectivity
0.00Solar Transmissivity
0.35
0.90
0.90
Inside Solar Reflectivity
Outside Long Wave Emissivity
Inside Long Wave Emissivity
Lights
Fluorescent, hung below ceiling, 100% load to space
%
0
1.00
SUSFLUOR
Fixture Type
Percent Lights to RA
Ballast Factor
67
0
%
%
Longwave Radiant Fraction
Shortwave Radiant Fraction
TRACE® 700 v6.2.7
Project Name
:
Veterans Expressway
Page 2 of 3
Dataset Name:
VETS XPRSWY GUNN HWY GANTRY.TRC
12