Specifications
Project: Ganrty Eq Bldg
Title: AET 6B Gantry Equip Build.
Type: Transportation
(WEA File: FL_TAMPA_INTERNATIONAL_AP.tm3)
CLP
(W)
Area or Length
or No. of Units
(Sqft or ft)
Allowance
(W/Unit)
CategoryDescription
External Lighting Compliance
ELPA
(W)
Tradable?
Ext Light 1 Building facades (by linear foot)
5.00
67.0
128
335
No
Tradable Surfaces: 0 (W) Allowance for Tradable: 750 (W)
All External Lighting: 128 (W)
Complicance check includes a excess/Base allowance of 750.00(W)
PASSES
Project: Ganrty Eq Bldg
Title: AET 6B Gantry Equip Build.
Type: Transportation
(WEA File: FL_TAMPA_INTERNATIONAL_AP.tm3)
Compli-
ance
Design
CP
Min
CP
Description
Acronym
Lighting Controls Compliance
Ashrae
ID
Area
(sq.ft)
1
Electrical Mechanical Equipment
Room - General
230
1
1
PASSES
Gantry Eq Bldg
PASSES
Project: Ganrty Eq Bldg
Title: AET 6B Gantry Equip Build.
Type: Transportation
(WEA File: FL_TAMPA_INTERNATIONAL_AP.tm3)
System Report Compliance
GEB AC-1 System 1 Single Package Vertical A/C
Component Category Capacity Design
Eff
Eff
Criteria
Design
IPLV
IPLV
Criteria
Comp-
liance
No. of Units
1
Cooling System
Air Conditioners Single
Package Vertical A/C
10.50 9.00
PASSES
Air Handling
System -Supply
Air Handler (Supply) -
Constant Volume
0.29 0.82
PASSES
PASSES
10/2/2012
EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
Page 5 of 7
22