Specifications

Project: Ganrty Eq Bldg
Title: AET 6B Gantry Equip Build.
Type: Transportation
(WEA File: FL_TAMPA_INTERNATIONAL_AP.tm3)
Other Required Compliance
Category Section Requirement (write N/A in box if not applicable) Check
Report 506.4.2 Input Report Print-Out from EnergyGauge FlaCom attached
Operations Manual
303.3.1,
503.2.9.3,
505.7.4.2
Operations manual provided to owner
Windows & Doors 502.3.2
Glazed swinging entrance & revolving doors: max. 1.0 cfm/ft²; all
other products: 0.3 cfm/ft²
Joints/Cracks 502.3.3 To be caulked, gasketed, weather-stripped or otherwise sealed
Dropped Ceiling Cavity 502.3
Vented: seal & insulated ceiling. Unvented seal & insulate roof &
side walls
HVAC Efficiency 503.2.3 Minimum efficiencies: Tables 503.2.3(1)-(8)
HVAC Controls 503.2.4
Zone controls prevent reheat (exceptions); separate thermostatic
control per zone;
Ventilation 503.2.5
Outdoor air supply & exhaust ducts shall have dampers that
automatically shut when systems or spaces served are not in use.
Exhaust air energy recovery required for cooling systems
(Exceptions).
ADS 503.2.7.5 Duct sizing and Design have been performed
HVAC Ducts 503.2.7
Air ducts, fittings, mechanical equipment & plenum chambers shall
be mechanically attached, sealed, insulated & installed per Table
503.2.7.2. Fan power limitations.
Balancing 503.2.9.1
HVAC distribution system(s) tested & balanced. Report in
construction documents.
Piping Insulation 503.2.8 HAC and service hot water. In accordance with Table 503.2.8.
Water Heaters 504
Performance requirements in accordance with Table 504.2. Heat
trap required.
Swimming Pools 504.7
Vapor-retardant or liquid cover or other means proven to reduce
heat loss on heated pools; Time switch (exceptions); readily
accessible on/off switch.
Motors 505.7.5 Motor efficiency criteria have been met
Lighting Controls 505.2, 502.3
Automatic control required for interior lighting in buildings >5,000
s.f.; Space control; Exterior photo sensor; Tandom wiring with 1 or
3 linear fluorescent lamps>30W
10/2/2012
EnergyGauge Summit® Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
Page 7 of 7
24
X
X
X
X
X
X
X
NA
NA
NA
NA
NA
X
X
X
X