Specifications

7 AVPA & HVEA PDS 1/2012 rev.1
Model Identification
A = Air Source Vertical Package
H = High Efficiency Vertical Package
Nominal Cooling
24 = 24,000 BTUH
30 = 30,000 BTUH
36 = 36,000 BTUH
42 = 42,000 BTUH
48/49 = 48,000 BTUH
60 = 60,000 BTUH
72 = 72,000 BTUH
System Type
Air Conditioner
Power Supply
A = 208/230V,1ø,60Hz
C = 208.230V,3ø,60Hz
D = 460V,3ø,60Hz
Configuration
N = ComPac
®
I A/C
C = ComPac
®
II A/C
Electric Heat kW
000 = No Heat 090 = 9 kW
040 = 4 kW 100 = 10 kW
050 = 5 kW 150 = 15 kW
080 - 8 kW
Special Option Code
R = Electric Reheat
U = Scroll Comp.
2-Stage
Compressor
Refrigerant
A = R410A
•VP S A • AC • • •
Certified Efficiency and Capacity Ratings at
ANSI/AHRI Standard 390 - AVPA Air Conditioners
Model Number
AVPA24 AVPA30 AVPA36 AVPA42 AVPA48 AVPA60 AVPA72 AVPA72
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
Cooling BTUH
1
24,000 29,000 35,000 42,000 46,500 54,500 62,000 70,000
EER
2
9.25 9.25 9.25 9.25 9.50 9.25 10.00 10.00
Rated Air Flow (CFM
3
) 840 1,000 1,220 1,575 1,760 1,850 2,050 2,050
ESP
4
@ Rated Conditions 0.10 0.15 0.15 0.15 0.20 0.20 0.20 0.20
1
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
2
EER=Energy Efciency Ratio
3
CFM=Cubic Feet per Minute
4
ESP=External Static Pressure
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect
performance and air ow.
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
AVPA Air Conditioners
Model Number
AVPA24 AVPA30 AVPA36 AVPA42 AVPA48 AVPA60 AVPA72 AVPA72
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
Total Capacity 24,000 29,000 35,000 42,000 46,500 54,500 62,000 70,000
Sensible Heat Ratio 0.71 0.75 0.69 0.75 0.76 0.72 0.71 0.66
Sensible Capacity 16,950 21,740 24,155 31,640 35,125 39,000 43,815 46,190
Rated Air Flow (CFM
1
) 840 1,000 1,220 1,575 1,760 1,850 2,050 2,050
1
CFM=Cubic Feet per Minute. Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
Cooling Performance (BTUH) at Various Outdoor Temperatures
-
AVPA Air Conditioners
Model Number
Outdoor Temperature
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC 100ºF / 38ºC 105ºF / 40.5ºC 110ºF / 43.3ºC 115ºF / 46ºC
AVPA24AC 27,840 26,880 25,920 24,960 24,000 23,040 22,080 21,120 20,640
AVPA30AC 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940
AVPA36AC 40,600 39,200 37,800 36,400 35,000 33,600 32,200 30,800 30,100
AVPA42AC 48,720 47,040 45,360 43,680 42,000 40,320 38,640 36,960 36,120
AVPA48AC 53,940 52,080 50,220 48,360 46,500 44,640 42,780 40,920 39,900
AVPA60AC 63,220 61,040 58,860 56,680 54,500 52,320 50,140 47,960 46,870
AVPA72ACA 71,920 69,440 66,960 64,480 62,000 59,520 57,040 54,560 53,320
AVPA72ACC, ACD 81,200 78,400 75,600 72,800 70,000 67,200 64,400 61,600 60,200
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
35