Specifications
Gunn Highway Entry and Exit Gantry Equipment Buildings:
1 – 16 KVA UPS 6,000 BTU/HR
1 – Toll Equipment Rack 2,500 Watts
1 – Communication Cabinet 2,500 Watts
1 – “C” Panel 150 Watts
1 – ATS 150 Watts
1 – SCADA Panel 300 Watts
Lights 1.7 Watts / Square Foot 390 Watts
Hutchison Road Entry and Exit Gantry Equipment Buildings:
1 – 16 KVA UPS 6,000 BTU/HR
1 – Toll Equipment Rack 2,500 Watts
1 – Communication Cabinet 2,500 Watts
1 – “C” Panel 150 Watts
1 – ATS 150 Watts
1 – SCADA Panel 300 Watts
Lights 1.7 Watts / Square Foot 390 Watts