Specifications
13 AVPA & HVEA PDS 1/2012 rev.1
Certified Efficiency and Capacity Ratings at
ANSI/AHRI Standard 390 for HVESA Air Conditioners
with 2-Stage Compressors
Model Number
HVESA36 HVESA42 HVESA49 HVESA60
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
Cooling BTUH
1
- 2nd Stage 35,000 39,000 47,000 56,000
EER
2
- 2nd Stage 11.00 10.50 11.75 10.50
Integrated Part Load Value
3
16.0 14.1 16.0 14.8
Rated Air Flow (CFM
4
) 1,300 1,400 1,750 1,900
ESP
5
@ Rated Conditions 0.15 0.15 0.20 0.20
1
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
2
EER=Energy Efciency Ratio
3
Integrated Part Load Value is an integrated efciency measure from 1st and 2nd stage capacity modulation.
4
CFM=Cubic Feet per Minute
5
ESP=External Static Pressure
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models. Operation of units at a different voltage from that of the rating point will affect
performance and air ow.
Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air Dry Bulb -
HVESA Air Conditioners with 2-Stage Compressors
Model Number
HVESA36 HVESA42 HVESA49 HVESA60
ACA ACC ACD ACA ACC ACD ACA ACC ACD ACA ACC ACD
Total Capacity 35,000 39,000 47,000 56,000
Sensible Heat Ratio 0.70 0.71 0.79 0.77
Sensible Capacity 24,445 27,590 36,920 43,235
Rated Air Flow (CFM
1
) 1,300 1,400 1,750 1,900
1
CFM=Cubic Feet per Minute
Sensible heat ratios based upon ANSI/AHRI std. 390 outdoor air conditions of 95°F (35°C) and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air.
Stage 2 Cooling Performance (BTUH) at
Various Outdoor Temperatures
Model Number
Outdoor Temperature
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC
HVESA36AC 40,600 39,200 37,800 36,400 35,000
HVESA42AC 45,240 43,680 42,120 40,560 39,000
HVESA49AC 54,520 52,640 50,760 48,880 47,000
HVESA60AC 64,960 62,720 60,480 58,240 56,000
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
Stage 1 Cooling Performance (BTUH) at
Various Outdoor Temperatures
Model Number
Outdoor Temperature
75ºF / 24ºC 80ºF / 26.5ºC 85ºF / 29ºC 90ºF / 32ºC 95ºF / 35ºC
HVESA36AC 30,856 29,792 28,728 27,664 26,600
HVESA42AC 34,336 33,152 31,968 30,784 29,600
HVESA49AC 44,080 42,560 41,040 39,520 38,000
HVESA60AC 51,040 49,280 47,520 45,760 44,000
Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67° WB (26.5°C DB/19.5°C WB) at various outdoor temperatures.
43