Specifications
AVPA & HVEA PDS 1/2012 rev.1 14
Electrical Characteristics - Compressor, Fan & Blower Motors -
HVESA Air Conditioner with 2-Stage Compressor
BASIC
MODEL
Type
COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR (ECM
6
)
VOLTS-HZ-PH RLA
1
LRA
2
VOLTS-HZ-PH RPM
3
FLA
4
HP
5
VOLTS-HZ-PH RPM
3
FLA
4
HP
5
HVESA36ACA
SCROLL
208/230-60-1 16.6 82.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA42ACA 208/230-60-1 16.6 96.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA49ACA 208/230-60-1 21.1 96.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA60ACA 208/230-60-1 25.6 118.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA36ACC
SCROLL
208/230-60-3 11.1 58.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA42ACC 208/230-60-3 13.4 88.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA49ACC 208/230-60-3 13.4 88.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA60ACC 208/230-60-3 17.6 123.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA36ACD
SCROLL
460-60-3 4.5 29.0 208/230-60-1 825 2.8
1/3 208/230-60-1 1500 2.8 1/2
HVESA42ACD 460-60-3 6.1 44.0 208/230-60-1 825 2.8 1/3 208/230-60-1 1500 2.8 1/2
HVESA49ACD 460-60-3 6.4 41.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
HVESA60ACD 460-60-3 9.0 62.0 208/230-60-1 825 2.8 1/2 208/230-60-1 1500 4.3 3/4
1
RLA = Rated Load Amps
2
LRA = Locked Rotor Amps
3
RPM = Revolutions per Minute
4
FLA = Full Load Amps
5
HP = Horsepower
6
ECM = Electronically Commutated Motor
The 460 volt units have a step down transformer for the 230 volt motors.
Summary Electrical Ratings (Wire Sizing) -
HVESA Air Conditioner with 2-Stage Compressor
Manual Damper (“N”) or Economizer (“C”)
ELECTRIC HEAT
000 =
None
040 = 4
kw
050 = 5
kw
060 = 6
kw
080 = 8
kw
090 = 9
kw
100 = 10
kw
120 = 12 kw 150 = 15 kw
BASIC
MODEL
VOLTAGE
PHASE
CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #1 CKT #2 CKT #1 CKT #2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
MCA
1
MFS
2
HVESA36ACA 208-230/1 26.4 40 26.4 40 28.8 40 34.1 40 44.4 45 n/a n/a 54.9 60 26.4 40 41.6 45 28.8 40 52.1 60
HVESA42ACA 208-230/1 26.4 40 n/a n/a 28.8 40 n/a n/a n/a n/a n/a n/a 54.9 60 26.4 40 41.6 45 28.8 40 52.1 60
HVESA49ACA 208-230/1 33.5 50 n/a n/a 33.5 50
n/a n/a n/a n/a n/a n/a 56.4 60 33.5 50 41.6 45 33.5 50 52.1 60
HVESA60ACA 208-230/1 39.4 60 n/a n/a 39.4 60 n/a n/a n/a n/a n/a n/a 56.4 60 39.4 60 41.6 45 39.4 60 52.1 60
HVESA36ACC 208-230/3 19.5 25 n/a n/a n/a n/a 20.8 25 n/a n/a 29.9 30 n/a n/a 38.9 40 n/a n/a 47.9 50 n/a n/a
HVESA42ACC 208-230/3 22.4 30 n/a n/a n/a n/a 22.4 30 n/a n/a 29.9 30 n/a n/a 38.9 40 n/a n/a 47.9 50 n/a n/a
HVESA49ACC 208-230/3 23.9 35 n/a n/a n/a n/a 23.9 35 n/a n/a 31.4 35 n/a n/a 40.4 45 n/a n/a 49.4 50 n/a n/a
HVESA60ACC 208-230/3 29.4 45 n/a n/a n/a n/a 30.0 45 n/a n/a 31.4 45 n/a n/a 40.4 45 n/a n/a 49.4 50
n/a n/a
HVESA36ACD 460/3 8.4 15 n/a n/a n/a n/a 10.4 15 n/a n/a 14.9 15 n/a n/a 19.4 20 n/a n/a 23.9 25 n/a n/a
HVESA42ACD 460/3 10.4 15 n/a n/a n/a n/a 10.4 15 n/a n/a 14.9 15 n/a n/a 19.4 20 n/a n/a 23.9 25 n/a n/a
HVESA49ACD 460/3 11.6 15 n/a n/a n/a n/a 11.6 15 n/a n/a 15.7 20 n/a n/a 20.2 25 n/a n/a 24.7 25 n/a n/a
HVESA60ACD 460/3 14.8 20 n/a n/a n/a n/a 14.8 20 n/a n/a 15.7 20 n/a n/a 20.2 25 n/a n/a 24.7 25 n/a n/a
1
MCA = Minimum Circuit Ampacity (Wiring Size Amps)
2
MFS = Maximum Fuse Size or HACR breaker
This chart should only be used as a guideline for estimating conductor size and overcurrent protection. Always refer to the data label on the unit for the requirements of the
specic unit. MCA & MFS are calculated at 230v. for the 208-230v units (A & C models) and at 460 volt for the 460v. units (D models).
All 460 units will have a step down transformer for the 230 volts motors.