Specifications

STANDARD CONSTRUCTION
FRAME
6" (152) deep, 6063T5 extruded aluminum with
.125" (3.2) nominal wall thickness. Downspouts
and caulking surfaces provided.
BLADES
Front stationary drainable blades – 6063T5
extruded aluminum with .081" (2.1) nominal wall
thickness, positioned at 37
1
/2° angle and spaced
approximately 6
1
/8" (156) on center. Rear
adjustable airfoil blades – 6063T5 extruded alu-
minum, .140" (3.6) nominal wall thickness.
SCREEN
5
/8" x .040" (16 x 1) expanded, flattened aluminum
bird screen in removable frame. Screen adds
approximately
1
/2" (13) to louver depth.
SEALS
Extruded vinyl blade edge seals on rear adjustable
blades and flexible, compressible aluminum jamb
seals.
LINKAGE
Concealed in frame.
BEARINGS
Stainless steel sleeve pressed into frame.
AXLES
1
/2" (13) plated steel hex.
ACTUATOR
Locking louver quadrant.
FINISH
Mill.
MINIMUM SIZE
12"w x 12"h (305 x 305).
APPROXIMATE SHIPPING WEIGHT
8 lbs. per sq. ft. (39.1 kg per m
2
).
MAXIMUM SIZE
55”w x 120"h (1397 x 3048) factory assembly,
unlimited width x 120"h field assembly. Louvers
larger than the maximum factory assembly size will
require field assembly of smaller sections.
INSTALLATION
The ELC6375DXD must be installed per the appro-
priate installation detail. Reference the appropriate
separate installation instruction sheet.
MULLION SUPPORTS
Factory installed mullion supports are provided at
rear of hidden mullions. Mullion depth = 1” (25) for
louvers 75
3
/4" (1924) tall and under. Depth = 5
1
/8"
(130) for louvers over 75
3
/4" (1924) tall.
ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. © Ruskin July 2009Spec ELC6375DXD-709/New
SIZE
TAG QTY. FRAME
A*-WIDE B*-HIGH
VARIATIONS
PROJECT LOCATION
ARCH./ENGR. CONTRACTOR
REPRESENTATIVE DATE
®
3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761-7476 • FAX (816) 765-8955
ELC6375DXD DRAINABLE COMBINATION LOUVER
MIAMI-DADE APPROVED
MIAMI-DADE COUNTY, FLORIDA NOTICE OF ACCEPTANCE NUMBER: 08.1211.05 (Expires 2/11/14)
Florida Product Approval #FL12232.1
LEED Material Information
VOC Content (g/L) - 0
Manufacturing Locations
(MR 5.1)
Geneva, AL 36340
Parsons, KS 67357
Recycled Content
(MR 4.1 & 4.2)
10% Post Consumer
30% Pre-Consumer
FEATURES
Approved for use in open structures
with provisions to manage weather
infiltration (wet rooms).
Maximum windload ±110 PSF (5.27
kPa).
44% free area in 48” x 48” (1.2 x 1.2)
size.
Published performance ratings based
on testing in accordance with AMCA
Publication 511.
Adjustable rear blades provide shut off
when desired.
Concealed blade linkage is protected
from weather exposure and reduces
required installation depth.
Blade and jamb seals provide tight clo-
sure.
High performance drainable frame and
blade system collects and removes
water providing excellent water pene-
tration performance.
VARIATIONS
Variations to the basic design of the louver are
available at additional cost. They include:
Extended sill.
Front or rear security bars.
Filter racks.
Installation angles.
A variety of bird and insect screens.
A selection of manual, electric, and pneumatic
actuators.
Selection of finishes: prime coat, baked
enamel (modified fluoropolymer), epoxy,
Pearledize, Kynar, clear and color anodize.
(Some variation in anodize color consistency
is possible).
Consult Ruskin for other special requirements.
Dimensions in inches, parenthesis ( ) indicate millimeters.
53