Specifications
WATER PENETRATION
Test size 48" wide x 48" high (1219 x 1219)
Beginning point of water penetration at .01 oz./sq. ft. is above 1250 fpm (381 m/min).
Oz. water/sq. ft of Free Area
15 min. test period
Free Area Velocity in feet per minute
Standard air .075 lb/cu. ft.
Ruskin Company certifies that the
ELC6375DXD louvers shown herein
are licensed to bear the AMCA Seal.
The ratings shown are based on
tests and procedures performed in
accordance with AMCA Publication
511 and comply with the require-
ments of the AMCA Certified Ratings
Program. The AMCA Certified Rat-
ings Seal applies to air performance
rating and water penetration ratings
only.
MIAMI-DADE COUNTY HURRICANE STRUCTURAL TEST PERFORMANCE
SIZES TESTED: 165”w x 75
3
/4"h (4391 x 1924) and 165”w x 120"h (4191 x 3048)
TAS 201-94 LARGE MISSILE IMPACT TEST
MISSILE TYPE
9 lb (4kg) Southern Pine 2" x 4" (51 x 102) 50 (15.24) 6
VELOCITY IN FT/SEC (M/SEC) IMPACTS
TAS 202-94 UNIFORM STATIC AIR PRESSURE TEST (LOUVER ONLY)
LOAD IN PSF (kPA)
+82.5 (+3.9)
-82.5 (-3.9)
+110.0 (+5.3)
-110.0 (-5.3)
+165.0 (+7.9)
-165.0 (-7.9)
30 seconds
30 seconds
30 seconds
30 seconds
30 seconds
30 seconds
100%
100%
100%
100%
100%
100%
LOAD DURATION LOUVER RECOVERY
TAS 203-94 CYCLIC WIND PRESSURE TEST
CYCLES LOAD IN PSF (kPA)
600
600
70
70
1
1
+55.0 (+2.6)
-55.0 (-2.6)
+66.0 (+3.2)
-66.0 (-3.2)
+143.0 (+6.8)
-143.0 (-6.8)
1 to 3 seconds
1 to 3 seconds
1 to 3 seconds
1 to 3 seconds
1 to 3 seconds
1 to 3 seconds
100%
100%
100%
100%
100%
100%
LOAD DURATION CYCLE LOUVER RECOVERY
54