Service manual

G.Fire Service Manual 20 Issue A — © Masport, March 2004
3. SERVICE ADJUSTMENTS
3.1 GAS PRESSURE ADJUSTMENT — CARDRONA and MONACO S2
All pressure adjustments must be made while the heater is operating.
Part or all of the right hand side panel of the cabinet may be removed to gain access to the gas
valve. See ACCESS POINTS on page 11.
GAS PRESSURES ECS II ACC STD
kPa
NG ULPG PROP NG ULPG PROP NG ULPG PROP
High Pressure 0.9 2.0 2.0 0.85 2.2 2.2 0.85 2.2 2.2
Turndown Pressure 0.35 0.5 0.5 0.43 1.36 1.36 0.23 0.7 0.7
3.1.1 STD MODELS. These have a pressure regulator separate from the control valve. Set the pressure
to the figures in the Table. The pressure test point is on the side of the regulator and the adjusting
screw is on the top.
1. Slacken the lock-nut and rotate the screw by hand, screwing in to increase the pressure.
2. After adjusting, tighten the lock nut and confirm the correct pressure.
3.
Use the
pressure test point on the
valve
to check the turndown
pressure. It is adjusted by turning
the small screw on the valve.
3.1.2 ACC MODELS. These have a pressure regulator inside the control valve. There are two test
points side by side on top of the control valve – the outlet pressure test point is the one closer to the
flame size control.
1.
If adjustment is necessary, uncouple the
control rod from the top of the flame size
control knob on the valve, extract the screw
down the
centre of this knob and pull the
knob off vertically.
2.
The high pressure is then set by rotating the
knurled plastic wheel exposed by removing
the knob.
3.
Once the pressure is correct (see Table),
care must be taken not to turn the plastic
wheel when the knob is re-fitted in its
maximum anti-clockwise position. This
position is set when the skirt of the knob
contacts the adjacent metal up-stand.
4.
After re-fitting, rotate the knob clockwise
and then fully anti-clockwise to verify that
the pressure is correct before replacing the
retaining screw and re-coupling the control
rod.
5. The turndown pressure is not independently adjustable. It should approximate the values shown in
the Table.