Instructions / Assembly

1. Ensure Proper Intake Ventilation... Always
ensure there is proper intake ventilation at the
soffit, undereave, and fascia areas of the roof. This
is required for a balanced ventilation system and to
help avoid premature ventilator motor failure. Use
the chart located on the outside of the package to
ensure the minimum recommended intake ventilation
is installed on the home. Always consult local building
codes for ventilation requirements.
2. Locate Position... Locate the ventilator as high as
possible on the roof, but not on the ridge line. The top
opening of the hood must be 24" (609 mm) BELOW
the ridge line (Figure 1a). Single ventilators should be
centered; multiple ventilators should be evenly spaced
over the length of the roof. Measure from the ridge line
to the top center of the ventilator hood (Figure 1b).
Using this measurement, go inside the attic and mark
the location centered between two rafters and drill a
hole. Put an object such as a pencil through the hole
so that it is visible on the outside (Figure 1c).
3. Mark and Cut Opening... Place and center the
template (included on the box) over the previous-
ly marked hole. Using a pencil or marker, use the
template as a guide to mark a circle. Note: Depending
on the ventilator model being installed, the included
cutout template on the box will be either 15" (381
mm) or 17" (432 mm) in diameter. For 24" (609 mm)
on-center rafters, make the cutout shown in Figure 2a.
For 16" (406 mm) on-center rafters, make the cutout
shown in Figure 2b. Using a power saber, jig saw, or
hand saw, cut out the opening (Figure 2c).
4. Prepare the Opening... Roll back and separate
any shingles (if existing). Remove all nails within 5 ½"
(140 mm) from the sides and top of the opening.
5. Test Ventilator Position... Test the final position of
the ventilator by sliding the flashing up under the upper
shingles. Trim any shingles as needed and remove the
ventilator (Figure 3a).
6. Seal and Fasten Ventilator... With the position
tested, apply a bead of roofing cement or urethane
sealant to the underside of the ventilator’s flashing.
Proceed with sliding the ventilator up under the top
shingles, with arrow on the flashing pointing up. Leave
the lower portion of the ventilator flashing on top of
the shingles for maximum weather resistance. Using
roofing nails, fasten the ventilator at all corners of the
flashing and approximately every 4" (102 mm) along
the edge of the flashing (Figure 3b).
Note: For maximum wind resistance, remove
the ventilator hood and fasten the flashing every
45 degrees, approximately 1" (25.4 mm) away
from the stack wall. Replace ventilator hood when
complete. Seal all exposed fasteners, flashing, stack
seams, and loose shingles.
Warning: Using excess roof cement may cause
blistering in the roofing shingles.
7. Wiring... Always disconnect power supply before
wiring the ventilator into an existing circuit. Remove
the thermostat cover and mount the thermostat box
to the edge of an adjacent rafter or stud using the
pre-punched holes. Make sure the thermostat element
opening on the back of the box isn’t covered. Each
ventilator must have its own thermostat. Leave the
flexible conduit with some slack and begin wiring the
thermostat as shown in Figure 4a (below).
Note: The included thermostat is adjustable from
60°F (15.5°C) to 120°F (48.8°C). The factory/
recommended setting for efficient operation is
105°F (40.5°C).
Note: In the unlikely event accessories or parts are
missing or this product does not operate correctly,
please contact Master Flow
®
Technical Services at
1-800-211-9612. Do NOT return this ventilator to
retailers or distributors.
Installation Instructions
For Roof-Mount Models: PR1, PR2, PR3,
ERV4, ERV5 & ERV6
MOTOR
POWER SOURCE
GREEN
GREEN
BLACK
BLACK
BLACK
BLACK
WHITE
WHITE
Figure 4a
Note: See Figures on previous page.
gaf.com