Press START: the machine will begin to discharge the air and the pressure value on the screen will gradually decrees.
Press STOP when the pressure is approximately 5 to 10 PSI higher than what the P/T chart say’s it should be for the temperature showing on the
screen. For example, if Tp is 140 PSI and the T is 80 degree F. The P/T chart say’s that the pressure at 80˚F should be 86.8 PSI. That means that
there is approximately 53 PSI of NCG. In this case, stopping the purge at 90-95 PSI will be sufficient enough for 69788 to operate properly while not
releasing too much refrigerant. It’s normal and unavoidable that a small amount of refrigerant is lost while purging.
NOTE: Purging to a pressure lower than what is determined from the P/T chart will result in a large loss of refrigerant.
Press RESET for MAIN MENU.
SETTINGS
LANGUAGE
Switch the machine on. The MAIN MENU will appear after a few seconds:
AUTOMATIC PROCEDURE
ASSISTED PROCEDURE
<NEXT MENU>
Ref avail X,XX lb
Select NEXT MENU, Press ENTER:
CALIBRATION
<DATA AND CONFIGURAT.>
SERVICE ALARM
TANK CHARGING
Select DATA AND CONFIGURAT., Press ENTER:
DATA
<CONFIGURATION>
SERVICES
PREVIOUS MENU
Select CONFIGURATION:
<LANGUAGE>
MEASURE UNITS
PREVIOUS MENU
Select LANGUAGE:
ENGLISH <-
ITALIANO
FRANCAIS
ESPANOL
NOTE: The current language is indicated by the symbol “<-“.
Use the ARROW keys to scroll the available languages. Confirm a language by pressing ENTER. The machine will reset and a few seconds later the
MAIN MENU will appear in the chosen language.
UNITS OF MEASUREMENT
Switch the machine on. The MAIN MENU will appear after a few seconds:
AUTOMATIC PROCEDURE
ASSISTED PROCEDURE
<NEXT MENU>
Ref avail X,XX lb
Select NEXT MENU: