Specification

3
DIMENSIONAL DATA*
CABINET
DUCT
OPENING
DUCT LOCATION
DRAIN
LOCATION
WET
MOD
ULE
MEDIA
DIMENSION
WATER
SERVICE
ELECTRIC
SERVICE
SKID
LOCATIONS
HW D A B C
(AS)
U
(AD)
P
(AU)
EFG JXYLMSTNQR
44 82 45 21 -
3
/
4
21-
3
/
4
13 -
19
/
32
21 -
11
/
32
N
/
A11
-
5
/
8
22
-
1
/
2
12
-
1
/
2
18
-
1
/
2
44 -
3
/
4
36 -
5
/
8
5
-
7
/
8
14
-
5
/
8
39
-
7
/
8
5
-
5
/
32
23 -
1
/
4
4 -
3
/
4
42
* All measurements in inches.
PUMP P/N VOLTS AMPS WATTS GPM (5FT. HEAD) BLOWER AND WET MODULE PART NUMBERS
110467 115 1.0 73 4.6 SIDE DISCHARGE BLOWER MODULE AS100B
110468 230 0.58 77 4.6 DOWN DISCHARGE BLOWER MODULE AD100B
2 Pumps Required. WET MODULE AS/AD100W
SPECIFICATIONS PERFORMANCE
Certified Air Delivery At .1” Increments Of External Static Pressure (Inches Static Pressure Water Gauge)
MAX
B.H.P.
OPER.
WGT.
AD
MODEL
BELT
AS
MODEL
BELT
0" 0.1" 0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 0.9" 1.0"
CFM RPM CFM RPM CFM RPM CFM RPM CFM RPM CFM RPM CFM RPM CFM RPM CFM RPM CFM RPM CFM RPM
1-1/2
706 A76 A82 6895 413 6720 419 6537 426 6350 434 6158 442 5962 452 5757 463 5540 475 5317 488 5076 502 4816 518
2
710 B77 B83 7589 455 7431 460 7266 466 7098 473 6925 480 6751 488 6571 497 6385 507 6195 517 5994 529 5786 541
3
723 B80 B86 8687 521 8555 525 8408 530 8262 535 8115 541 7966 548 7812 555 7657 562 7501 570 7341 579 7174 588
5
739 B81 B87
10300
617
10190
621
10069
625
9945
629 9823 634 9698 639 9573 644 9448 649 9317 655 9189 661 9057 668
Performance certi ed is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances
(accessories). Models AS/AD 100 include the affects of an 8 inch thick evaporative media on the inlet. When the Cooler Model No, Motor H.P., & Blower Speed are determined from the
SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table below.
MOTOR SPECIFICATIONS
BLOWER MOTORS
VOLTS PHASE
MOTOR
AMPS*
SHAFT
DIA.
MOTOR
WGT(LB)
MOTOR
PART NO.
BLOWER MOTORS
VOLTS PHASE
MOTOR
AMPS*
SHAFT
DIA.
MOTOR
WGT(LB)
MOTOR
PART NO.
H.P. SPEED H.P. SPEED
1-1/2 1
115/208-230
1
20/11-10
5/8 41 110459-1 2 1
230/460
3
6.8/3.4
7/8 44 110464-9
1-1/2 1
200
3
6.9
7/8 40 110463-92 3 1
200
3
11.0
1-1/8 83 110465-92
1-1/2 1
230/460
3
6/3
7/8 40 110463-9 3 1
230/460
3
9.6/4.8
1-1/8 83 110465-9
21
115/208-230
1
24/13.2-12
5/8 49 110460-1 5 1
200 3 17.5 1-1/8 87 110466-92
21
200
3
7.8
7/8 44 110464-92 5 1
230/460
3
15.2/7.6
1-1/8 87 110466-9
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
SHEAVE SELECTION
MOTOR
H.P.
MAUREY
SHEAVE
SHEAVE
BORE
AD
MODEL
BELT
AS
MODEL
BELT
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
CHAMPION-AD
PULLEY-BELT
KIT NO.
CHAMPION-AS
PULLEY-BELT
KIT NO.
121110987654321
1-1/2
D8450 5/8* A76 A82 391 401 412 422 433 443 454 464 475 485 496 506 3DI-11 3DI-31
1-1/2
D8450 7/8* A76 A82 391 401 412 422 433 443 454 464 475 485 496 506 3DI-10 3DI-30
2
D8450 5/8* B77 B83 414 424 434 445 455 465 475 485 495 506 516 526 3DI-16 3DI-36
2
D8450 7/8* B77 B83 414 424 434 445 455 465 475 485 495 506 516 526 3DI-15 3DI-35
3
D8550 1-1/8 B80 B86 482 492 502 513 523 533 543 553 563 574 584 594 3DI-20 3DI-40
5
D8600 1-1/8 B81 B87 549 559 569 580 590 600 610 620 630 641 651 661 3DI-25 3DI-45
*When selecting motor, be sure to select Pulley-Belt Kit with same pulley bore as shaft size of motor selected.
SIZING TABLES
OUTDOOR
DRY BULB
TEMP.
1-1/2 H.P. MOTOR / CFM-SP* 2 H.P. MOTOR / CFM-SP* 3 H.P. MOTOR / CFM-SP* 5 H.P. MOTOR / CFM-SP*
6895 / 0 5962 / .5 4816 /1.0 7589 / 0 6751 / .5 5786/1.0 8687/ 0 7966 / .5 7174/ 1.0 10300 /0 9698/ .5 9057 / 1.0
OUTDOOR WET-BULB OUTDOOR WET-BULB OUTDOOR WET-BULB OUTDOOR WET-BULB
75
65 55
75 65 55 75 65 55 75
65 55
75 65 55 75 65 55 75
65 55
75 65 55 75 65 55 75
65 55
75 65 55 75 65 55
85
LAT
GPH
77
7
69
14
60
20
77
6
68
12
60
18
76
5
68
9
59
14
77
8
69
15
61
22
77
7
69
13
60
20
77
6
68
11
60
17
77
9
69
17
61
26
77
8
69
16
61
24
77
7
69
14
60
21
77
10
69
20
62
31
77
10
69
19
61
28
77
9
69
18
61
27
95
LAT
GPH
79
14
70
20
62
27
78
12
70
18
61
23
78
9
69
14
60
19
79
15
71
22
62
30
79
13
70
20
62
27
78
11
69
17
61
23
79
17
71
26
63
34
79
16
71
24
63
32
79
14
70
21
62
28
79
20
72
31
64
41
79
19
71
28
63
38
79
18
71
27
63
36
105
LAT
GPH
80
20
72
27
80
18
71
23
79
14
71
19
81
22
74
30
80
20
72
27
79
17
71
23
81
26
73
34
81
24
73
32
80
21
72
28
82
31
74
41
81
28
73
38
81
27
73
36
115
LAT
GPH
82
27
74
34
81
23
73
29
80
19
72
24
82
30
74
37
82
27
74
33
81
23
72
28
83
34
75
43
83
32
74
39
82
28
74
35
84
41
76
51
83
38
75
48
83
36
75
45
* Static pressure (inches of water). GPH = water consum at design conditions but does not include bleed-off amount. Amount of bleed-off will vary with
different water sources, but an amount equal to 10% of water consumption at any design condition suf cient for average water.
LAT=Cooler Discharge Temperature
.
COMMERCIALSPECIFICATIONS GUIDE
Series AS/AD 100
AD OUTLET
EEA
Q
X
D
G
F
G
D
S
Q
W
R
C
J
J
N
P
B
B
A
L
MM
E
E
N
Y
L
P
D
H
U
B
T
AD OUTLET
C
TOP VIEW
WEIV EDISWEIV TNORF
BLOWER
SECTION
AS OUTLET
AU OUTLET