Secure Power Always Series A from 700 to 3000 VA UPS Catalogue
Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products are for installation, operation and maintenance. Product designations All product designations used are trademarks or product names of Chloride Group PLC or its subsidiary companies. This publication is issued to provide outline information and is not deemed to form any part of any offer or contract.
Uninterruptible Power Supply UPS Catalogue • 2009 Series A from 700 VA to 3000 VA 1. SCOPE 2 2. SYSTEM DESCRIPTION 2 3. DEVICE DESCRIPTION 3 4. GENERAL REQUIREMENTS 4 5. BATTERY MANAGEMENT 4 6. CONTROL PANEL 5 7. REAR SIDE 6 8. INTERFACES & CONNECTIVITY 8 9. MECHANICAL DATA 9 10. TECHNICAL DATA 11. OPTIONS 01 9 10 MKA4CAT0UKAG4MG/Rev.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 1. SCOPE This document describes a continuous duty single-phase output, on-line double conversion uninterruptible power supply ( U P S ) s ys t e m . Th e U P S s h a l l automatically provide continuity of electrical power, within defined limits and without interruption, upon failure or degradation of the commercial AC source.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 3. DEVICE DESCRIPTION 3.1 Components/blocks CHARGER The charger includes a temperature compensation which regulates the charging process. When the mains voltage is within tolerances, the charger provides a nominal recharge current up to 1.2A to the batteries. This element is current-limited; therefore, it can only provide the nominal current, although batteries may demand more current. Typical recharge time for internal batteries is 4 hours (for 90% recharge).
MASTERGUARD Series A UPS from 700 VA to 3000 VA 4. GENERAL REQUIREMENTS 4.1 Standards and certifications accordance with the following international standards: MASTERGUARD GmbH is certified by the German TÜV as a company with a quality and environmental management system in accordance with standards ISO 9001 and ISO 14001.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 5. BATTERY MANAGEMENT 2000 VA models UPS UPS + 1BP UPS + 2BP UPS + 3BP UPS + 4BP 800 W 15 min 58 min 108 min 177 min 213 min 320 W 37 min 163 min 236 min 358 min 445 min 1120 W 11 min 40 min 73 min 114 min 166 min 5.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 6. CONTROL PANEL Front panel with LCD display for tower models Front panel with LCD display for rack/tower models 7. REAR SIDE The following figures show different rear sides for Series A depending on the housing and power ratings. All models include RS232 and USB (HID) communication ports, providing the user more flexibility in order to obtain information regarding monitoring. Legend: 1. Communication slot 2. Fan 3. Fan (In other models, only one fan) 4.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 7. REAR SIDE Series A Tower 1500 Legend: 1. Communication slot 2. Input circuit breaker 3. Input power socket (10A) 4. Not controllable output sockets (10A) 5. Controllable outlets (2 groups,10A) 6. USB port 7. RS232 port (DB9) 8. Fan 9. External battery pack connection 10. RJ11 port for battery pack detection cable 11. ROO/RPO terminals 12. Earth Screw Battery Pack Series A 1000/1500 RT Legend: 1. Battery pack connector 2.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 8. INTERFACES & CONNECTIVITY Series A shall be equipped with DB9 and USB communication ports and a slot for inserting advanced communication cards. These interfaces can be used for: RS232 signals (RxD and TxD) and 5 output signals. They shall be available as opto-coupled, open collector signals. Pin distribution shall be as indicated in figure “DB9 pin distribution”.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 9. MECHANICAL DATA 9.1 Enclosure 9.2 Ventilation 9.3 Installation of rack/tower units The UPS shall be housed in an enclosure with removable front panels (UPS internal batteries shall be accessible from the front panel) and IP20 protection. Standard colour of the enclosure shall be RAL7016 (grey anthracite), thus providing an optimum alternative for most environments.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 10. TECHNICAL DATA CONNECTIONS Input Output 6 x IEC320 C13 (10A), (2 groups contr.
MASTERGUARD Series A UPS from 700 VA to 3000 VA 11. OPTIONS 11.3 ManageUPS CIO 11.4 MopUPS Professional Series A shall be compatible with MopUPS Professional is optional software for Series A. Its primary function is the safe shutdown of the operating system of an unattended computer in the event of a power failure. All files will be closed and directory pointers will be written to disk while the system operates from UPS battery power. ManageUPS CIO software.
NOTE MKA4CAT0UKAG4MG/Rev.
MKA4L0UKAG4MG For a full list of contacts please visite our website at www.chloridepower.com Certificate No. EMS 76732 Certificate No.