Installation Manual
30 
ChargeMaster Plus 12/75-3, 12/100-3, 24/40-3, 24/60-3 – User and Installation Manual 
6  TROUBLE SHOOTING 
The  ChargeMaster  Plus  is  protected  against  overload,  short  circuit,  overheating  and  under  and over 
voltage. If a fault condition occurs, the LEDs indicate an error code. See section Status display for an 
explanation. 
CAUTION! 
The ChargeMaster Plus is not protected against serious over voltage (>275VAC) on 
the AC input. 
If you cannot solve a problem using the fault-finding table, contact your supplier or Mastervolt. Make sure 
you have the part and serial number at hand. 
Malfunction 
Possible cause 
What to do 
No output voltage and/or 
current 
No AC input 
Check AC wiring, check remote 
control panel 
AC input voltage too low (< 
75VAC) 
Check input voltage, check generator 
AC input frequency out of 
range 
Check input voltage, check generator 
Output voltage too low, 
charger supplies maximum 
current 
Load connected to the 
batteries is larger than charger 
can supply 
Reduce load taken from the batteries 
Batteries not 100% charged 
Measure battery voltage. After some 
time this will be higher 
Wrong setting of the charge 
voltage 
Check settings (see chapter 4) 
Charge current too low 
Batteries almost fully charged 
Nothing, this is normal when the 
battery is almost fully charged 
High ambient temperature 
Nothing; if ambient temperature is 
more than the setting limit, the 
charge current is automatically 
reduced 
Low AC input voltage. At lower 
AC input voltages, the charge 
current is reduced 
Check AC input voltage 
Batteries not fully charged 
Charge current too low 
See “Charge current too low” in this 
table 
Current to load is too high 
Reduce load taken from the batteries 
Charge time too short 
Use a battery charger with higher 
capacity 
Battery temperature too low 
Use the battery temperature sensor 
Defective or old battery 
Check battery and replace if 
necessary 
Wrong setting of the charge 
voltage 
Check settings (see chapter 4) 










