Product Manual
AC Master 12/300, 12/500, 24/300, 24/500 – User and Installation Manual
7
Step 7. Connect the battery to the DC input. Do not place the fuse yet!
Step 8. Wire the IEC plug.
See also figure Connections on page 5.
Front view of the IEC C14 male plug
Step 9. Connect the AC load.
For safe installation:
• The neutral conductor (N) of the AC output of
the AC Master must be connected to the safety
ground (PE/GND).
• Integrate a ground fault circuit-interrupter
(GFCI/RCD) in the wiring of the AC output.
Refer to locally applicable regulations on these
issues!
Step 10. Check all wiring. When all wiring is OK: place the DC fuse(s) and close the fuse cover.
When the fuse is placed, internal capacitors may cause a spark. This is normal.
Step 11. Switch ON the AC Master.
ON
OFF
POWER SAVING