Product Specifications
Specifications
General specifications
Output voltage 200/220/230/240 V - 50/60 Hz (selectable)
Output waveform true sine
Nominal battery voltage 12 V
Recommended battery capacity >= 160 Ah
Continuous power at 25 °C / 77 °F, cos phi 1 1500 W
Continuous power at 40 °C / 104 °F, cos phi 1 1500 W
Peak load (1 min.) < 1730 W
Peak load (1 s) < 2650 W
AC connection plug connection EU (Schuko), with UK plug (code 28211500) or with
NZ/AU plug (code 28411500)
Galvanic isolation yes
Efficiency 93 %
Display/read-out LED indication: battery voltage, load level, status
Alarms potential free alarm contact
Dimensions, hxwxd 248 x 421 x 83 mm
9.8 x 16.6 x 3.3 inch
Weight 4.2 kg
9.3 lb
Compliance CE, E-mark, RCM
Technical specifications
Technology high frequency, input & output fully isolated
Low battery voltage, switches off at 10.5 V
Low battery voltage, switches on at 12.5 V
High battery voltage, switches off at 16.5 V
High battery voltage, switches on at 14.5 V
Input current (nominal load) 150 A
No-load power consumption (ON mode) < 1.8 A
No-load power consumption (energy saving mode) < 0.1 A
Minimal DC fuse (slow blow) 175 A
Minimal cable size 50 mm²
Harmonic distortion typical < 3 %
Cos phi all power factors allowed
Temperature range (ambient temp.) -20 °C to 60 °C, derating power > 40 °C
-4 to 140 °F
Cooling temperature and load controlled fan
Protection degree IP21, horizontal wall mounting
Protections over-temperature, overload, short circuit, high/low voltage, reverse
polarity (fuse)
MasterBus compatible yes, using a MasterBus AC Master Interface