User`s guide
9 xPC Target Web Browser Interface
9-12
3 In the Target selection section, access levels are set in the RTW system
target file
box. For example, to set the access level to 1, enter
xpctarget.tlc -axpcWWWAccessLevel=1
The effect of not specifying -axpcWWWAccessLevel is that the highest access
level (0) is set.
4 Click OK.
The various fields disappear, depending on the access level. For example, if
your access level does not allow you access to the parameters, you do not see
the button for parameters.
There are various access levels for monitoring, which allow different levels of
hiding. The proposed setup is described below. Each level builds on the
previous one, so only the incremental hiding of each successive level is
described.
Level 0 — Full access to all panes and functions.
Level 1 — Cannot change the sample and stop times. Cannot change
parameters, but can view parameters.
Level 2 — Cannot start and stop execution of the target application or log data.
Level 3 — Cannot view parameters. Cannot add new scopes, but can edit
existing scopes.
Level 4 — Cannot edit existing scopes on the Scopes pane. Cannot add or
remove signals on the
Scopes pane. Cannot view the Signals pane and the
Parameters pane, and cannot get scope data.