Analog Inputs
There must be 2 analog inputs that support 4-20mA current loops.
Controller Outputs
Solid State Outputs
The proximity detection system must provide at least 3 Solid-state relay outputs. These solid-state digital
outputs must provide 24VDC when activated and must be able to supply up to 50mA individually at
nominal voltage (each must be able to source up to 1.2W).
Analog Outputs
There must be 2 analog outputs that support 4-20mA current loops.