Specification
Gas Types Flammable Toxic x 2 Oxygen
Sensors and measuring range CH
4
= 0-100% LEL CO/H
2
S = 0-500/0-100ppm 0-25% by volume
Measuring principal Catalytic Combustion Electro-chemical Electro-chemical
Calibration gasses % = up to 50% full-scale ppm = 20-200 Bottled / Fresh Air
Response time T90 Less than 15 seconds Less than 35 seconds Less than 15 sec.
Resolution 0.1% < 6 ppm 0.1%
Long term drift ± 0.1% 2% Full scale /month 2% Full scale/month
Min & max pressure - 10 KPa to + 50 KPa Ambient ± 10% Ambient ± 10%
Max relative humidity 95 % Non-condensing
Sample velocity 20-40 liters per hour
Operating temperature -10 to + 40
o
C
Storage temperature 0 20
o
C
Power source * Battery pack 3.7 Volt 2,800 mAmp/hour
OR
*Battery pack 3.7 Volt 3.200 mAmp/hour
Operational time > than 12 hours
Real Time Clock accuracy < 10 ppm (< 0.32%)
Dimensions 125 x 75x 39 (mm)
Weight 320 g
Housing Polycarbonate with TPE over-mold
Warranty * 1 (one) year on all electronic parts and workmanship
* 6 (six) months on battery pack
* 3 (three) months on sensors fitted by OEM
Approval SANS/IEC 60079 Part 0: 2005
SANS/IEC 60079 Part 11: 2007
SANS/IEC 60079 Part 29 - 1
SANS 1515 1
SANS 1515 3 part 1
User specification SANS/IEC 60079 Part 29 - 2