Technical data

SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
238 System Manual, 07/2009, C79000-G8976-C222-07
Range of
values:
TRUE or FALSE
No parameter specified: Default value FALSE is valid.
With this parameter, you can specify whether the integration principle is
used in threshold value processing.
If no parameter is specified, the default is FALSE; in other words, threshold
values are processed without integration. This corresponds to the previous
ST1 procedure. In this case, you can also expect less traffic on the
telecontrol line and locally between CPU and TIM (over the MPI bus or party
line).
Note
When MeanValueGeneration = TRUE, i.e. the analog values are sent as mean values, the
ThresholdIntegration parameter has no meaning.
Name: ZeroLimitation
Declaration: INPUT
Data type BOOL
Default: TRUE
Explanation Zero limitation.
Range of
values:
TRUE or FALSE
No parameter specified: Default value TRUE is valid.
This parameter allows you to specify whether negative values should be
suppressed and replaced with the value 0.
If no parameter is specified, the default is TRUE. This means that the lowest
value is limited to 0.
Name: TriggerInput
Declaration: INPUT
Data type BOOL
Default: FALSE
Explanation Trigger input.
Range of
values:
Input
Bit memory
Data bit
No parameter specified:
Default value FALSE is valid.
I 0.0 ... I n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
If required, this parameter can be used to specify an input over which the
user can trigger the transmission *) of the analog value message at any time
(signal edge from 0 to 1).