Specifications

16
Installation,OperationandMaintenanceManual
MatrixxMX-100,MX-150,MX-200System
ValveCycleSettingsforSofteners
MODEL
VALVECYCLESETTINGS(MINUTES)
INJECTOR
SIZE
DRAINLINE
FLOWCONTROL
(GPM)
BRINELINE
FLOWCONTROL
(GPM)
CLEANWATER
PROBLEMWATER
BACKWASH
BRINE/RINSE
RINSE
BACKWASH
BRINE/RINSE
RINSE
IWT565-75
5.0
50.0
5.0
10.0
50.0
5.0
#00
#1(1.5)
0.70
IWT565-100
5.0
50.0
5.0
10.0
50.0
5.0
#0
#2(2.0)
0.70
IWT565-150
5.0
50.0
5.0
10.0
50.0
5.0
#1
#3(2.4)
0.70
IWT565-200
5.0
50.0
5.0
10.0
50.0
5.0
#2
#4(3.5)
0.70
IWT565-250
5.0
50.0
5.0
10.0
50.0
5.0
#2
#6(4.0)
0.70
IWT565-300
5.0
50.0
5.0
10.0
50.0
5.0
#3
#7(5.0)
0.70
IWT565-75C
5.0
50.0
5.0
10.0
50.0
5.0
#00
#2(2.0)
0.70
IWT565-100C
5.0
50.0
5.0
10.0
50.0
5.0
#0
#3(2.4)
0.70
Figure13.ValveCycleSettings
ChangingValveCycleSettings
1. Pressthe“MENU”forthreesecondstounlockscreen.
2. Pressandhold“UPandDOWN”forthreesecondstoenterLevelTwoMasterProgramming.
3. Pressthe“DOWN”andadvancetotheBACKWASHmenuoption.Press“SET/REGEN”toedittheBACKWASH
minutes.Press“UPorDOWN”arrowstochangetheBACKWASHminutevalues.Press“SET/REGEN”againtoac
ceptthenewvalue.
4. Pressthe“DOWN”twicetoadvancetotheRINSEmenuoption.Press”SET/REGEN”toedittheRINSEminutes.
Press”UPorDOWN”arrowtochangetheRINSEminutevalues.Press”SET/REGEN”againtoacceptthenewvalue.
5. Press“MENU”toexitprogrammingmode.