Technical data

16 HN.50.Y1.02
The following functions are provided to enable
servicing and fault location on PVG CIP:
Activation of PVE
Diagnosing
Restoring factory settings
Enable PVE This function is used for servicing. It activates
or deactivates individual PVE signals, i.e.
when the function is deactivated, a neutral
signal is sent to the PVE irrespective of the
received CAN message.
Units -
Max. 1 (activated)
Min. 0 (deactivated)
Standard 1
Precision 1
OD index 201B HEX
Diagnosing When diagnosing it is possible to see the last
25 faults and their types. See fault types under
“Safety aspects”, page 9.
Note: The value 0 signifies no fault.
OD index 1003 HEX
Fault location/service
parameters
The float position control function makes it
possible to connect ports A and B to tank.
This is performed mechanically by a specially
designed spool. Two steps are necessary to
activate the function:
1. The proportional function connected to the
float position control function must be
established.
OD index 2104 HEX
OD index 2105 HEX
The signal for the float position PVE must
be activated say more than x% in the
direction of port B.
Units [%]-
Max. 100
Min. 10
Standard 10
Precision 1
OD index 201D HEX
Power save time Defines the time delay from inactivity (PVE
signal = neutral) until power to the PVEs is cut
off (individually).
Units [s]
Max. 20
Min. 0 (not connected)
Standard 0
Precision 1
OD index 201C HEX
The function can be deactivated in two ways:
• If the joystick is moved towards port A by
a signal of more than 10%.
• If the joystick is within 10% signal to both
ports A and B and the button is activated.
2. The button used to activate the float posi-
tion is mapped.
Float position control
function