Operating instructions

Commissioning
32
6.3.4 Digital input - DIGITAL INP./M5
The settings for the digital status inputs, e.g. for monitoring pumps, starting/stopping the
counter or resetting the min/max-value memory are grouped in this section.
!
Note!
The digital inputs 1 to 4 are permanently assigned to relays 1 to 4 in the PUMP function.
Relay 1 is monitored by digital input 1, relay 2 by digital input 2 etc.
When the "Batch" function is used, digital input 1 is permanently assigned to a preset value
count function. Configuration for this digital input is then not possible.
Function
(menu
item)
Parameter setting Description
Function
Off
Pump
Res Tot. (*)
Start/Stop (*)
Res MinMax
Function of the selected digital input.
•Off
Pump = pump monitoring (see Pump monitoring
function)
Res Tot. = reset the totalizer*
Start/Stop = start or stop the totalizer*
Res MinMax = reset the min/max memory values
!
Note!
Parameters marked with an asterisk (*) are only
available for the pulse output option if this function has
been configured.
Level
Low
High
Selects the side for evaluation.
Low = descending side
High = increasing side
Sampl. time
0..99
0
Defines the time (in seconds) within which pump
feedback at the digital input is to be expected. If there
is no feedback within the defined time, an error
message is generated and a second pump is activated if
more than one pump is available.
!
Note!
The sampl. time setting is used to specify the
monitoring behavior of the digital input!
Sampl. time = 0 means fault monitoring
Sampl. time <> 0 means operation monitoring