Operating instructions

Commissioning
40
Grad operating mode
G09-RIA452ZZ-15-00-xx-en-006
Fig. 17: Grad operating mode
The "Grad" operating mode is used for monitoring the changes in the input signal over time. The
time basis T
m
of the monitoring system is configured in the "PARAMETER/M55 -> Grad. time"
menu.
The difference between the lower range value M
0-m
and the upper range value M
0
of the interval
is calculated. If the calculated value is greater that the value set under "Setpoint A", the relay is
switched in accordance with the failsafe mode configured in "Rel. Mode" (see Page 56).
The relay is switched on again once the difference between M
1-m
and M
1
drops below the value
set in "Hysteresis". The sign determines the direction of signal change. Positive values monitor
an increase in the measured value while negative values monitor a decrease. A new value is
calculated every second (floating interval).
The following parameters must be configured:
Alarm operating mode
A relay with the "Alarm" operating mode is activated if the following events occur:
Analog input (4-20 mA) < 3.6 mA (lower Namur limit) or > 21.0 mA (upper Namur limit)
Menu Function (menu item) Setting value
LIMIT 1 to 8/M10 to 17 Function
Setpoint A
Hysteresis
Grad. time
Grad
Gradient value for threshold
Value for hysteresis
Interval time in seconds