Simplifying System IntegrationTM 6612_OMU_S2_URT_V1_13 Firmware Description Document December 21, 2009 Rev. 1.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 © 2009 Teridian Semiconductor Corporation. All rights reserved. Teridian Semiconductor Corporation is a registered trademark of Teridian Semiconductor Corporation. Simplifying System Integration is a trademark of Teridian Semiconductor Corporation. All other trademarks are the property of their respective owners.
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document Table of Contents 1 Introduction ................................................................................................................................... 5 2 Description of Basic Measurement Equations ............................................................................. 5 3 Serial Communication ...................................................................................................................
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 Tables Table 1: Measurement Equations Definitions ........................................................................................... 5 Table 2: Outlet 1 MPU Outputs for Narrowband Method......................................................................... 17 Table 3: Outlet 1 MPU Outputs for Wideband Method ............................................................................
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document 1 Introduction This document describes the firmware 6612_OMU_S2_URT_V1_13, which can be used with the Teridian 78M6612 dual outlet power and energy measurement IC. This firmware is designed for single phase measurement systems using current shunts as the current sensors, but current transformer sensors may also be used if desired.
612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 3 Serial Communication The serial communication with the 78M6612 takes place over a UART (UART0) interface. The default settings for the UART of the 78M6612 are given below: Baud Rate: Data Bits: Parity: Stop Bits: Flow Control: 38400bps 8 None 1 Xon/Xoff The host’s serial interface port is required to implement these settings on its UART.
FDD_6612_ 010 4.2 6612_OMU_S2_URT_V1_13 Firmware Description Document Reset Commands A soft reset of the 78M6612 can be performed by using the Z command. The soft reset restarts code execution at addr 0000 but does not alter flash contents. To issue a soft reset to the 78M6612, the host sends the following: >Z The W command acts like a hardware reset. The energy accumulators in XRAM will retain their values. Z Reset Description: Allows the user to cause soft resets. Usage: Z Soft reset.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 4.3.3 Block Reads The block read command can also be used to read consecutive registers: )saddr:eaddr? For decimal format or )saddr:eaddr$ for hex format where saddr is the start address and eaddr is the final address. The following block read command requests the Outlet 1 wideband information contained in Table 4 in decimal format: >)20:3D? 4.3.4 Concatenated Reads Multiple commands can also be added on a single line.
FDD_6612_ 010 Examples: 6612_OMU_S2_URT_V1_13 Firmware Description Document )08$ Reads data word 0x08 in hex format. )08$$ Reads data words 0x08, 0x09 in hex format. )08$$$ Reads data words 0x08, 0x09, 0x0A in hex format. )28:4D$ Read Outlet 1 narrowband data words in hex. )08? Reads data word 0x08 in decimal format. )08?? Reads data words 0x08, 0x09 in decimal format. )08??? Reads data words 0x08, 0x09, 0x0A in decimal format.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 Auxiliary Description: Various Commands: , Typing a comma (“,”) repeats the command issued from the previous command line. This is very helpful when examining the value at a certain address over time, such as the CE DRAM address for the temperature. / The slash (“/”) is useful to separate comments from commands when sending macro text files via the serial interface. All characters in a line after the slash are ignored. 4.
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document The device will calibrate the temperature, calibrate the voltage, and finally calibrate the power and save all values to flash. The commands are summarized in the table below: CALx Complete Calibration Commands Description: Allows the user to Calibrate the IC. Usage: CAL Calibrates temperature, then voltage, and finally current for Outlet 1. CAL2 Calibrates temperature, then voltage, and finally current for Outlet 2.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 4.5.2.3 CLT Command The CLT command is used for the temperature calibration. With this command, the contents of CE register 71 are read and entered into MPU register C0 and the contents are saved to flash.
FDD_6612_ 010 4.6 6612_OMU_S2_URT_V1_13 Firmware Description Document CE Data Access Commands The CE is the main signal processing unit in the 78M6612. The user writes to the CE data space are mainly for calibration purposes. The 78M6612 OMU demo units and 78M6612 AC-PMON demo units come pre-calibrated. No user writes to the CE data space are necessary. For the advanced user, details of CE data access commands are given.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 4.6.3 U Command The U command is used for updating default values of the CE Data in flash. The description is given in the CE control Command section. Additional examples are provided in the table that follows: ] CE Data Access Description: Allows user to read from and write to CE data space. Usage: ] {Starting CE Data Address}{option}…{option} Command Combinations: ]saddr? Read 32-bit word in decimal.
FDD_6612_ 010 4.7 6612_OMU_S2_URT_V1_13 Firmware Description Document CE Control Commands The most pertinent command is the enable command, CEn. It is mainly used to turn the CE on or off such that the CE data contents can be updated in flash using the U command. The CE is normally on but in order to update the CE data entry, the CE must first be turned off using the CE0. 4.7.1 CE Data Write If the cal coefficient for the IA current input is changed: >]08=FFFFC9B0 4.7.
6612_OMU_S2_URT_V1_13 Firmware Description Document 4.8 FDD_6612_010 I/O RAM (Configuration RAM) Command The RI command is used for altering the I/O RAM contents. This is usually not necessary as the FW defaults these settings appropriately. One case where the RI command could be used would be to speed up the accumulation interval for energy measurements.
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document 5 MPU Measurement Outputs This section describes the measurement outputs that can be obtained. Energy outputs are accumulated numbers. The default accumulation interval is 1 second (999.75 ms). The host accessing the measurement information from the 78M6612 more frequently will not result in any update in the information. The accumulation interval is set by the following: 0.
6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment FDD_6612_010 Example Bit 12 – PFA_WB positive – Wideband Power Factor Positive Threshold Alarm for Outlet 1. Bit 13 – MAXIB_NB – maximum narrowband current exceeded on Outlet 2. Bit 14 – MAXIB_WB – maximum wideband current exceeded on Outlet 2. Bit 15 – PFB_NB negative – Narrowband Power Factor Negative Threshold Alarm for Outlet 2.
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Watts A 07 mW Outlet 1 active power measurement (per second). Wh A 08 mWh Outlet 1 active accumulated energy measurement (per hour). Total Cost A 09 mUnits Outlet 1 cost of Wh A. Irms_nb A 0A mArms Outlet 1 narrowband rms current measurement. VARs_nb A 0B mW Outlet 1 narrowband reactive power measurement (per second).
6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment Watts A Min 12 mW Minimum Outlet 1 active power measured (per second). Watts A Max 13 mW Maximum Outlet 1 active power measured (per second). Irms_nb A Min 14 mArms Outlet 1 minimum narrowband rms current measured. Irms_nb A Max 15 mArms Outlet 1 maximum narrowband rms current measured. VARs_nb A Min 16 mW Outlet 1 minimum narrowband reactive power measured (per second).
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Example Phase Angle_nb A Max 1D – Outlet 1 maximum narrowband phase angle measured. Reserved 1E Reserved Reserved 1F – – If the maximum narrowband phase angle measured on Outlet 1 is 70 degrees )1D? Returns: +70.000 Reserved Reserved Reserved Table 3 lists the wideband measurement outputs for Outlet 1.
6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment FDD_6612_010 Example Bit 14 – MAXIB_WB – maximum wideband current exceeded on Outlet 2. Bit 15 – PFB_NB negative – Narrowband Power Factor Negative Threshold Alarm for Outlet 2. Bit 16 – PFB_NB positive – Narrowband Power Factor Positive Threshold Alarm for Outlet 2. Bit 17 – PFB_WB negative – Wideband Power Factor Negative Threshold Alarm for Outlet 2.
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Wh A 28 mWh Outlet 1 active accumulated energy measurement (per hour). Note: Duplicate of address 0x08 (see Table 2). Total Cost A 29 mUnits Outlet 1 cost of Wh A. Note: Duplicate of address 0x09 (see Table 2). Irms_wb A 2A mA Outlet 1 wideband rms current measurement. VARs_wb A 2B mW Outlet 1 wideband reactive power measurement (per second).
6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment Watts A Max 33 mW Maximum Outlet 1 active power measured (per second) Note: Duplicate of address 0x13 (see Table 2). Irms_wb A Min 34 mArms Outlet 1 minimum wideband rms current measured. Irms_wb A Max 35 mArms Outlet 1 maximum wideband rms current measured. VARs_wb A Min 36 mW Outlet 1 minimum wideband reactive power measured (per second).
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment Example Reserved 3F – Reserved Reserved Table 4 lists the narrowband measurement outputs for Outlet 2. Table 4: Outlet 2 MPU Outputs for Narrowband Method Output Location (hex) LSB Comment Delta Temperature 40 0.1 °C Temperature difference from 22° C. Note: Duplicate of address 0x00 (see Table 2). Line Frequency 41 0.1 Hz Line Frequency Note: Duplicate of address 0x01 (see Table 2).
6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment FDD_6612_010 Example Bit 15 – PFB_NB negative – Narrowband Power Factor Negative Threshold Alarm for Outlet 2. Bit 16 – PFB_NB positive – Narrowband Power Factor Positive Threshold Alarm for Outlet 2. Bit 17 – PFB_WB negative – Wideband Power Factor Negative Threshold Alarm for Outlet 2. Bit 18– PFB_WB positive – Wideband Power Factor Positive Threshold Alarm for Outlet 2.
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Wh B 48 mWh Outlet 2 active accumulated energy measurement (per hour). Total Cost B 49 mUnits Outlet 2 cost of Wh B. Irms_nb B 4A mArms Outlet 2 narrowband rms current measurement. VARs_nb B 4B mW Outlet 2 narrowband reactive power measurement (per second). VAs_nb B 4C mW Outlet 2 narrowband apparent power measurement (per second). – Outlet 2 narrowband power factor.
6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment Watts B Max 53 mW Maximum Outlet 2 active power measured (per second). Irms_nb B Min 54 mArms Outlet 2 minimum narrowband rms current measured. Irms_nb B Max 55 mArms Outlet 2 maximum narrowband rms current measured. VARs_nb B Min 56 mW Outlet 2 minimum narrowband reactive power measured (per second). VARs_nb B Max 57 mW Outlet 2 maximum narrowband reactive power measured (per second).
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Phase Angle_nb B Max 5D – Reserved 5E Reserved 5F – – Rev. 1.1 Comment Example Reserved If the maximum narrowband phase angle measured on Outlet 2 is 70 degrees )5D? Returns: +70.000 Reserved Reserved Reserved Outlet 2 maximum narrowband phase angle measured.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 Table 5 lists the wideband measurement outputs for Outlet 2. Table 5: Outlet 2 MPU Outputs for Wideband Method Output Location (hex) LSB Comment Delta Temperature 60 0.1 °C Temperature difference from 22° C. Note: Duplicate of address 0x00 (see Table 2). Line Frequency 61 0.1 Hz Line Frequency Note: Duplicate of address 0x01 (see Table 2). Alarm Status 30 62 Definition for Status Register Bit 0 – Minimum Temperature Alarm.
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Example Bit 17 – PFB_WB negative – Wideband Power Factor Negative Threshold Alarm for Outlet 2. Bit 18– PFB_WB positive – Wideband Power Factor Positive Threshold Alarm for Outlet 2. Bit 19 – MAXIT_WB – maximum total wideband current exceeded on both Outlet 1 and Outlet 2. Bit 20 – MAXIT_NB – maximum total narrowband current exceeded on both Outlet 1 and Outlet 2.
6612_OMU_S2_URT_V1_13 Firmware Description Document Output Location (hex) LSB Comment Irms_wb B 6A mArms Outlet 2 wideband rms current measurement. VARs_wb B 6B mW Outlet 2 wideband reactive power measurement (per second). VAs_wb B 6C mW Outlet 2 wideband apparent power measurement (per second). – Outlet 2 wideband power factor. The output will be between -0.950 and 1.000. Positive power factor is defined as current lagging voltage (inductive).
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Reserved If the largest wideband current measured on Outlet 2 is 30 Amps )75? Returns: +30.000 If the largest VARs measured on Outlet 2 is 80 VARs )76? Returns: +80.000 If the largest VARs measured on Outlet 2 is 300 VARs )77? Returns: +300.000 If the smallest VAs measured on Outlet 2 is 80 VARs )78? Returns: +80.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 Table 6 lists the narrowband measurement outputs for both outlets combined (Outlet 1 + Outlet 2). Table 6: Combined Outlets MPU Outputs for Narrowband Method Output Location (hex) LSB Comment Watts T 80 mW Active power measurement (per second) on both outlets. Wh T 81 mWh Active accumulated energy measurement (per hour) on both outlets. Total Cost T 82 mUnits Total Cost of Wh for both outlets.
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Irms_nb T Max 8B mArms Maximum combined outlet narrowband rms current measured. VARs_nb T Min 8C mW Minimum combined outlet narrowband reactive power measured (per second). VARs_nb T Max 8D mW Maximum combined outlet narrowband reactive power measured (per second). VAs_nb T Min 8E mW Minimum combined outlet narrowband apparent power measured (per second).
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 Table 7 lists the wideband measurement outputs for both outlets combined (Outlet 1 + Outlet 2). Table 7: Combined Outlets MPU Outputs for Wideband Method Output Watts T Location (hex) 90 LSB mW Comment Example Active power measurement (per second) on both outlets. Note: Duplicate of address 0x80 (see Table 6). If 120 Watts are measured on both outlets )90? Returns: +120.
FDD_6612_ 010 Output 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Comment Irms_wb T Max 9B mArms Maximum combined outlet wideband rms current measured. VARs_wb T Min 9C mW Minimum combined outlet wideband reactive power measured (per second). VARs_wb T Max 9D mW Maximum combined outlet wideband reactive power measured (per second). VAs_wb T Min 9E mW Minimum combined outlet wideband apparent power measured (per second).
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 6 Configuration Parameter Entry 6.1 MPU Parameters Table 8 lists the MPU parameters that the Firmware 6612_OMU_S2_URT_V1_13 has configured. The user does not need to alter any of these parameters while using the demo unit. Table 8: MPU Parameters MPU Parameter VMAX A Location (hex) A0 LSB mVrms Default Comment +600.000 External rms voltage corresponding to 250 mVpk at the VA input of the 78M6612.
FDD_6612_ 010 MPU Parameter 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Default Comment Example Temp_raw_x reading at 22 °C. Needed to enable temperature compensation. Temp _raw_x is obtained from the CE: ]71? This value is then entered here: )A6=+value in decimal Also, the command: >CLT Will do the same as the steps above. Temperature Nominal A6 – Reserved A7 – PPMC A8 ppm/° C -668 ppm per °C.
6612_OMU_S2_URT_V1_13 Firmware Description Document MPU Parameter Location (hex) LSB Default De-Energize Delay AF ms +0.000 Reserved B0 - BC ppb 0 Additional Status BD – Unused BE – Unused BF – Reserved C0 – Calibration Voltage C1 mVrms Comment Parameter given in relay manufacturer’s data sheet is entered here. The amount of delay will be 1 ms plus the value entered in )AF. Reserved 1 Bit 0 – Reserved. Bit 1 – WPULSE Disable. Bit 2 – VCal Failure. Bit 3 – ICal1 Failure.
FDD_6612_ 010 MPU Parameter Average Count for Current Max Iteration for Voltage Max Iteration for Current Tolerance on Watts Average Count for Watts Max Iteration for Watts Calibration WRATE Calibration Temperature Rev. 1.1 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) C7 C8 C9 CA CB CC CD CE LSB 1 1 1 mW 1 1 1 0.
6612_OMU_S2_URT_V1_13 Firmware Description Document MPU Parameter Location (hex) LSB Unused CF – Unused 0.1°C Minimum Temperature Alarm Threshold. A temperature below this threshold will set the alarm (bit 0 of the Alarm Status Register). Temp Alarm Min Threshold Temp Alarm Max Threshold Frequency Minimum Threshold Frequency Maximum Threshold SAG Voltage Alarm Threshold Min Voltage Alarm Threshold D0 D1 D2 D3 D4 D5 0.1°C 0.1Hz 0.1Hz mVpk mVrms Default +0.0°C +70°C +59.0 +61.
FDD_6612_ 010 MPU Parameter Peak IA_wb Alarm Threshold 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) D9 LSB mArms Default +15.000 Comment Example Maximum Wideband Current measured on the IA channel above which a flag must set (bit 8 of the Alarm Status Register). If the peak wideband current threshold on Outlet 1 is to be changed from the default value of 15 Amps to 30 Amps then set as follows: )D9=+30.000 PFA_nb_Neg Threshold PFA_nb_Pos Threshold DA DB – – -0.
6612_OMU_S2_URT_V1_13 Firmware Description Document MPU Parameter Peak IB_wb Alarm Threshold Location (hex) DF LSB mArms Default +15.000 FDD_6612_010 Comment Example Maximum Wideband Current measured on the IB channel above which a flag must set (bit 14 of the Alarm Status Register). If the peak wideband current threshold on Outlet 2 is to be changed from the default value of 15 Amps to 30 Amps then set as follows: )DF=+30.000 PFB_nb_Neg Threshold PFB_nb_Pos Threshold E0 E1 – – -0.
FDD_6612_ 010 MPU Parameter Peak I Total_wb Alarm Threshold 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) E5 LSB mArms Default +20.000 Comment Example Maximum Wideband Current measured on Outlet 1 plus Outlet 2 above which a flag must be set (bit 20 of the Alarm Status Register). If the wideband peak current threshold on Outlet 1 plus Outlet 2 is to be changed from the default value of 20 Amps to 30 Amps then set as follows: )E5=+30.
6612_OMU_S2_URT_V1_13 Firmware Description Document 6.2 FDD_6612_010 CE Parameters Table 9 lists the CE parameters that the Firmware 6612_OMU_S2_URT_V1_13 has set. The user does not need to alter any of these parameters. Table 9: CE Parameters CE Parameter CAL IA CAL IB CAL VA CAL VB PHASE_ ADJ_IA 46 Location (hex) LSB 08 16384 is the default and is a gain of 1. 32767 is max giving a gain of 2. +13873 Gain constant for IA input. 09 16384 is the default and is a gain of 1.
FDD_6612_ 010 CE Parameter PHASE_ ADJ_IB 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB 0D -16384 ≤ PHASE_ ADJ_IB ≤ +16384 Default Comment Example 0 Outlet 2 Phase adjustment =15 * PHASE_ADJ_IB * 2-14 (degrees) No adjustment should be necessary when using current shunts. SAG CNT Bits 15:8 – determines the consecutive voltage samples below SAG_Threshold before a sag alarm is declared. 255 is the maximum value.
6612_OMU_S2_URT_V1_13 Firmware Description Document CE Parameter SAG Threshold QUANTA QUANTB QUANT VAR A QUANT VAR B Location (hex) LSB Default 11 The voltage threshold for VMAX A SAG warnings. *4.2551E- +313350 The default value 07 (Vpk) is 80 Vpk if VMAX = 600 V. 12 VMAX A * IMAX A * 1.8541E10 (Watt) 13 VMAX A * IMAX B * 1.8541E10 (Watt) 14 15 VMAX A * IMAX A * 1.8541E10 (Watt) VMAX A * IMAX B * 1.8541E10 (Watt) 0 Compensation added to the Watt calculation for Outlet 1.
FDD_6612_ 010 CE Parameter 6612_OMU_S2_URT_V1_13 Firmware Description Document Location (hex) LSB Default Comment 0 IA input compensation added for input noise and truncation in the squaring 2 calculation for I . Used for compensation at low current levels. Keep below 10000d. – Reserved 2 QUANT IB 17 (IMAX B) * 4.6351E-11 2 (A ) Reserved 18 – Example Reserved To increase all channels equally by 1% scale the nominal number, 16384 by 1/(1-0.01).
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 7 Address Content Summary If the color shading is the same, the information in the table cells is the same between narrowband and wideband measurements. Note that Outlet 1 = channel A and Outlet 2 = channel B.
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document Outlet 2 Common Data Common, Outlet 2 Specific Data Tier 1, Outlet 2 Specific Data Tier 2, Outlet 2 Specific Max/Min Data Rev. 1.
6612_OMU_S2_URT_V1_13 Firmware Description Document Totals of Multiple Outlets Common Total Data FDD_6612_010 Narrowband Wideband 80 Total Watts 90 Total Watts 81 Total Energy 91 Total Energy 82 Total Cost 92 Total Cost 83 Total Current 93 Total Current 84 Total VARs 94 Total VARs 85 Total VA's 95 Total VA's 86 Total Over Current Count 96 Total Over Current Count 87 (Reserved for Future) 97 (Reserved for Future) Common Total Max/Min Data 88 Total Watts Min 98 Total W
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document Table 11: MPU Input Summary Chart Voltage A0 Vmax Current - Outlet 1 A1 Imin (Creep A) - Outlet1 A2 Imax (A) - Outlet1 A3 Imin (Creep B) - Outlet2 A4 Imax (B) - Outlet2 Unused A5 Unused Temperature A6 TEMPERATURE NOMINAL A7 Reserved A8 PPMC Current - Outlet 2 Cost Relay Configuration A9 PPMC2 AA Cost per KWh AB Cost Unit string AC Polarity, Latch type AD Sequence Delay AE Energize Delay AF Denergize Dela
6612_OMU_S2_URT_V1_13 Firmware Description Document Voltage D4 SAG Voltage Alarm Threshold D5 Min Voltage Alarm Threshold D6 Max Voltage Alarm Threshold Unused D7 Unused Current - Outlet 1 D8 Max Current Alarm Threshold (NB) D9 Max Current Alarm Threshold (WB) DA Power Factor Alarm - Threshold (NB) DB Power Factor Alarm + Threshold (NB) DC Power Factor Alarm - Threshold (WB) DD Power Factor Alarm + Threshold (WB) DE Max Current Alarm Threshold (NB) DF Max Current Alarm Threshold (W
FDD_6612_ 010 6612_OMU_S2_URT_V1_13 Firmware Description Document 8 Contact Information For more information about Teridian Semiconductor products or to check the availability of the 78M6612, contact us at: http://www.teridian.com/contact-us/ 6440 Oak Canyon Road Suite 100 Irvine, CA 92618-5201 Telephone: (714) 508-8800 FAX: (714) 508-8878 Rev. 1.
6612_OMU_S2_URT_V1_13 Firmware Description Document FDD_6612_010 Revision History Revision Date Description 1.0 7/29/2009 First publication. 1.1 12/21/2009 In Section 1, deleted “The OMU demo units are typically pre-loaded with the “H” version, but both versions are provided in the demo kit’s CDs.” In Table 1, corrected the Narrowband Equation and the Wideband Equation for Symbol P. In Section 4.3.1, added “When requesting information in decimal, the data is preceded by a + or a -.