User guide

6613_PSU_1+1S_URT_V1_00 Firmware Description Document UG_6613_040
24 Rev. 1.0
MPU
Parameter
Location
(hex)
LSB Default Comment Example
Cost/kWh AA mUnits +0.150
Cost per kWh (kilowatt hour) in
milliunits.
If the cost per kWh is to be
10 units:
)AD=+10.000<CR>
Units of Cost AB N/A USD
4-byte string describing unit of
cost
(e.g. USD, EURO etc.). There
must be 4 characters. If entering
US dollars, USD, there needs to
be a space after the D to make it a
four character string.
To enter US Dollars:
)AB=”USD “<CR>
To enter Euros:
)AB=”EURO”<CR>
Reserved A0 - BC 0 Reserved Reserved
Additional
Status
BD 1
Bit 0 Reserved.
Bit 1 WPULSE Disable.
Bit 2VCal Failure.
Bit 3 ICal1 Failure.
Bit 4 WCal1 Failure.
Unused BE
Tolerance on
Phase
BF 0.001° 0.100°
Measured value to fall within this
set tolerance of the target value
(Calibration Current entry) for the
calibration to be complete.
If the tolerance to the target
phase is desired to be more
coarse, to within 0.5°, the
user can enter the
following:
>)BF=+0.500<CR>
Reserved C0 0 Reserved Reserved
Calibration
Voltage
C1 mVrms +120.000
Target line voltage (rms) used for
calibration.
If the target line voltage for
calibration is 220V, enter
the following:
>)C1=+220<CR>