Datasheet

Table Of Contents
Data Sheet 71M6531D/F-71M6532D/F FDS 6531/6532 005
54 Rev 2
2 Functional Description
2.1 Theory of Operation
The energy delivered by a power source into a load can be expressed as:
=
t
dttItVE
0
)()(
Assuming phase angles are constant, the following formulae apply:
P = Real Energy [Wh] = V * A * cos φ* t
Q = Reactive Energy [VARh] = V * A * sin φ * t
S = Apparent Energy [VAh] =
22
QP +
For a practical meter, not only voltage and current amplitudes, but also phase angles and harmonic content
may change constantly. Thus, simple RMS measurements are inherently inaccurate. A modern solid-state
electricity meter IC such as the 71M6531 functions by emulating the integral operation above, i.e. it pro-
cesses current and voltage samples through an ADC at a constant frequency. As long as the ADC resolu-
tion is high enough and the sample frequency is beyond the harmonic range of interest, the current and
voltage samples, multiplied with the time period of sampling will yield an accurate quantity for the momen-
tary energy. Summing up the momentary energy quantities over time will result in accumulated energy.
Figure 18: Voltage, Current, Momentary and Accumulated Energy
Figure 18 shows the shapes of V(t), I(t), the momentary power and the accumulated power, resulting from
50 samples of the voltage and current signals over a period of 20 ms. The application of 240 VAC and 100 A
results in an accumulation of 480 Ws (= 0.133 Wh) over the 20 ms period, as indicated by the accumulated
power curve. The described sampling method works reliably, even in the presence of dynamic phase shift
and harmonic distortion.