Datasheet

73S8010C Data Sheet DS_8010C_024
12 Rev. 1.5
Figure 5: Power Down Mode Operation
7 Over-temperature Monitor
A built-in detector monitors die temperature. When an over-temperature condition occurs (most likely
resulting from a heavily loaded card interface, including short circuits), a card deactivation sequence is
initiated, and a fault condition is reported to the system controller (bit 4 of the status register is set and
generates an interrupt).
8 Activation Sequence
After Power on Reset, the INT signal is low until V
DD
is stable. When V
DD
has been stable for
approximately 10 ms and the INT signal is high, the system controller may read the status register to see
if the card is present. If all the status bits are satisfactory, the system controller can initiate the activation
sequence by writing a ‘1’ to the Start/Stop bit (bit 0 of the Control register).
The following steps and Figure 6 show the activation sequence and the timing of the card control signals
when the system controller initiates the Start/Stop bit (bit 0) of the control register:
1. Voltage V
CC
to the card should be valid by the end of t
1
. If V
CC
is not valid for any reason, then the
session is aborted.
2. Turn I/O to reception mode at the end of t
1
.
3. CLK is applied to the card at the end of t
2
.
4. RST (to the card) is set high at the end of t
3
.
Figure 6: Activation Sequence
PRES
INT
PWRDN
Internal RC OSC
Start/Stop bit
OFF follows PRES regardless of PWRDN
PWRDN during a card
session has no effect
After setting PWRDN = 0,
the controller must wait at
least 10ms before setting
Start/Stop = 1
EMV / ISO deactivation
time ~= 100 uS
~10ms
PWRDN has effect when
the cardi s deactivated
t
1
= 0.510 ms (timing by 1.5 MHz internal Oscillator), I/O in reception mode
t
2
0.5 μs, CLK starts
t
3
≥ 42000 card clock cycles, RST set high