Specifications

m
CORPORATION
MUNCIE, INDIANA, USA
INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES
Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice.
Electro-Mechanical Valves Page 6100-S-1
Installation Instructions
B. Teflon tape acts as a lubricant and greatly
reduces the pipe wrench turning force re-
quired to seal the threads.
Take care not to overtighten threads as
this can damage the valve.
C. Good piping practice dictates that piping be
independently supported, so that valve bodies
are not placed in a bind. In addition, large
valves may require support.
D. Clean pipe lines of foreign materials before
installing valve into line.
For new installations, a gas filter or strainer shall be
installed in the fuel gas piping to protect the
downstream safety shut-off valves.
per NFPA 86-4-2.4.3 (1999)
NFPA 86C-4-2.4.3 (1999)
NFPA 86D-4-2.4-3 (1999)
If normal inlet pressure to the fuel pressure regula-
tor immediately upstream from the valve exceeds
the valve’s pressure rating, a relief valve shall be
provided and it shall be vented to a safe location.
per NFPA 86-5-7.1.7 (1999)
NFPA 86C-5-7.1.7 (1999)
NFPA 86D-5-7.1.7 (1999)
E. Mount valve so that open/shut window
indicator [1] will be visible to your operating
personnel. The open/shut window indicator
should never face downward. With Maxon
electro-mechanical top assemblies, the motor
access side plate [2] should always be
vertical to the ground. Valves are usually
installed in horizontal piping; however, other
1/00
1. Read complete instructions before proceeding
and do not discard packing materials until any/all
loose items are located. Also, make sure that the
installation of the Maxon valves will be in compli-
ance with all applicable governmental, insurance
and/or agency requirements or codes, such as
NFPA-70, National Electric Code, CSA C22.1,
Canadian Electric Code, etc.
2. General considerations:
A. Prior to shipment, each valve is operated
electrically and cycled at rated and 1-1/2
rated pressure while being leak tested. Every
Maxon valve is operationally tested and
meets the requirements of ANSI B16.104
Class VI Seat Leakage when it leaves our
plant.
B. Inspect your valve for any shipping damage.
Contact Maxon Corporation with the valve’s
serial number (printed on the valve's name-
plate) for replacement and/or repair parts.
C. Read the nameplate on your valve. This
gives the maximum pressure, temperature
limitation, voltage requirements and service
conditions of your specific valve. DO NOT
exceed nameplate ratings.
D. Select mounting location carefully. Your
Maxon valve is designed to operate for many
years if installed in a location that is cool,
clean and dry.
3. Pipe the valve in the direction of the flow arrow
[3] on the valve body. The Maxon valve body can
shut off flow in one direction only.
A. Remove all thread and flange protectors
before installing valve in your service line.
1
2
3
4
5
1
2
3
4
5
1
2
4
5

Summary of content (14 pages)