Driver - Fuji PLC
There are currently 2 Fuji PLC drivers - Micrex-F and NJ Series. The following information applies to both
PLC types.
Tx Micrex / Tx Fuji NJ
Transmits up to 58 consecutive local registers from a Kingfisher RTU to a Fuji PLC. Returns a response
code in the first network register corresponding to the address assigned to the Fuji PLC.
Comment: A 12-character description.
PLC number: (1-249) The RTU address assigned to the Fuji PLC.
RTU Source: (#R1 to #R2048) The starting local register to transmit to the Fuji PLC.
PLC Destination: The data address in the Fuji PLC to write the data to. Eg. K0
Number of registers: (1-58) Number of registers to be written to the Fuji PLC.
Rx Micrex / Rx Fuji NJ
Reads up to 106 consecutive registers from a Fuji PLC and stores them in the RTU's network registers.
Returns a response code in the first network register corresponding to the address assigned to the Fuji PLC.
Comment: A 12-character description.
PLC number: (1-249) The RTU address assigned to the Fuji PLC.
PLC Source Address: The starting address in the Fuji PLC from where the data is read. Eg. BD12.
RTU Destination: (#R2 to #R1024) Specified as a local register but indicates the first network register to
begin storing the data from. Note: the first network register is reserved for the response code returned by the
PLC after each message.
Number of registers: (1-58) Number of registers to read.