6.
When the message
“Download speed will be set to
115.2k Baud!” appears select
OK
7.
If the message “No response
from RTU in Monitor Mode!
appears, select Abort
Toolbox 32 is using the wrong
baud rate. From Configuration,
PC Setup select another Baud
Rate and return to step 2 above.
Note: the baud rate of the RTU
port can be determined from the
configuration file that was last
running in the CP-10/11.
8.
While downloading firmware
locally, the Rx LED for Port 1 of
the CP-10/11 will stay on.
OK
L1
L2
Vbak
Rx
Rx
Rx
RTS
RTS
RTS
CD
CD
CD
CP-11
P1
Tx
P2
Tx
P3
Tx
9.
After a successful download
the following message will be
displayed.
Note: The RTU configuration will
now need to be downloaded
since downloading firmware cold
starts the RTU and clears the
existing configuration.