Remaining Online
To remain online after connection, set On Line Inactivity to 0 and Hang Up After to 0 in both RTUs in the
PSTN link. If the line is disconnected, the RTU will reconnect when the next TX or RX message is initiated
from ladder logic.
Init String: (0-29 characters) These characters are sent to the modem to initialise it after startup, after
disconnection and if a dial attempt fails. The default initialisation strings for each type of modem can be
obtained by selecting the appropriate button below the Initialisation String field and are listed below.
Modem Default Initialisation String
3G Modem
(Maxon Modmax
MM-6280IND)
[blank]. The default string should be removed for the modem to function
correctly. Note: modem parameters must be set and saved in the modem
using a terminal program. Please see the topic Example - Modems.
External Modem or
GSM (eg. Banksia
modem or
Wavecom GSM)
#
AT&FTE0V0S0=2&W
V34-D Option
Board
#
AT&FTE0V0S0=2&W
X3 can be added to the above string if the modem is unable to recognize the
dial tone or is experiencing problems establishing a connection ie.
AT&FTE0V0S0=2X3&W
V22-D Option Board
(superseded)
AT&FTE0V0S0=2&C1&W
&C1 = track DCD from remote
For this option board, the port baud rate should be set to 2400 bps (or lower).
LP-1 Falcom GSM
(superseded)
AT@|+CICB=0|+CBST=7|+DS=0|&W
LP-1 interprets the above string as separate AT commands as shown below:
ATE0%C0\N0S0=2&D2 <Enter>
AT+CICB=0 <Enter>
AT+CBST=7 <Enter>
AT+DS=0 <Enter>
AT&W
The @ character is replaced by E0%C0\N0S0=2&D2 by the LP-1 (this keeps
the initialisation string below the 29-character limit). &D2 allows the RTU to
hang up the GSM using DTR. +CICB=0|+CBST=7|+DS=0 sets the GSM to
9600 baud data mode. The | character is replaced by a carriage return and AT
by the LP-1.
#
Dialing A Paging Service: If experiencing problems, error correction may need to be disabled by including \N0 ie.
AT&FE0V0S0=2\N0&W. If experiencing problems when using an MC module and a Dial option board, the baudrate may
need to be limited to 9600 by including F8 in the initialisation string ie. AT&FE0V0S0=2F8&W. When using a recent Dial
option board, the RTU port baudrate may need to be set to 2400 baud. Older Dial option boards can use 9600 bps.