Staco FirstLine PL UPS Technical Specications
UPS Rating kVA/kW 10/9 15/13.5 20/18 30/27
40/36
Input
Topology On-Line Double Conversion
Voltage 208Y/120 VAC, Three Phase, 4 wire plus ground or 220Y/127 VAC configurable from the Front Panel
Range +15% / -20% Battery Discharge@-15% with full load
Frequency 60/50Hz +/- 5.0 Hz
Power Factor 0.99 at 100% load, 0.98 minimum at 50% load
Current Distortion (THD) <1% @100% Load, <2% @ 50% Load, <5% @ 10% Load
Input Current (A)
Nominal: 28
Maximum: 33
Nominal: 42
Maximum: 49
Nominal: 55
Maximum: 65
Nominal: 83
Maximum: 97
Nominal: 111
Maximum: 130
Input Current Inrush Walk-In from 25% maximum to 100% full load rating in 5 seconds
Output
Voltage 208Y/120 VAC, Three Phase, 4 wire plus ground or 220Y/127 VAC configurable from the Front Panel
Static Voltage Regulation +/- 2%
Voltage Transient Response
Voltage transient response shall not exceed the following, and shall recover to 95% within 10 milliseconds:
a) +/- 15% at the first cycle for a 100% step load b) +/- 1% (loss or return of AC input)
Frequency
(inverter synchronous)
60/50Hz (tracks frequency of static bypass source) +/- 0.5, 1.0, 2.0, 5.0 Hz (user settable)
Frequency Slew Rate (inverter
synchronized to static bypass)
± 10 Hz per second
Free Running Frequency
(on battery or asynchronous)
60/50Hz +/- 0.01Hz
Voltage Distortion THD Less than 1% (Linear load), less than 2% with crest factor 2.5 to 1
Inverter Overload 125% for 10 minutes, 150% for 60 seconds
Bypass Overload 400% for 10 seconds, 1000% for half line cycle
Bypass Input – Range
Synchronization Voltage
+12% / -15%
Bypass Input Frequency
Tracking Range
+/- 5Hz
Overall Efficiency Up to 94%
Output Current (A) 28 42 55 83
111
Heat Rejection (BTU/Hr) 3,412 5,118 6,824 10,237
13,649
Battery Run Time (minutes)
Internal Battery String
Model (-X)
(-1) 37, (-2) 18, (-3) 9 (-1) 21, (-2) 10, (-3) 4 (-1) 14, (-2) 6 (-1) 8
(-1) 4
Environmental
Altitude De-rate load capability above 1000 meters, 1% per 100 meters
Operating Temperature 40 °C Maximum
Audible Noise
@ 3 feet "A" weighted scale
61dBA 67dBA
Dimensions and Weights
H x W x D inches (mm)
41.7 (1059) x 20.3 (516) x 33 (838) 52 (1321) x 23.2 (589) x 33 (838)
- (X) model, Lbs. (kg)
-0, 410 (186) -1, 950 (431)
-2, 735 (334) -3, 630 (286)
-0, 585 (266)
-1, 1,125 (510)
-0, 585 (266)
-1, 1,185 (538)
Standard Communications
SNMP/WEB SNMP Card & UPS PowerView Pro Shutdown and Monitoring Software for Windows/Novell
Modbus Monitoring & Control via RS-485/RTU Protocol/Read Holding and Write Registersl
Options
Input/Output 480/480V (D or Y), 480V/208V (D or Y) with Transformer option
Standards
208V Model
UL listed to 1778, CUL to CSA C22.2, NEMA PE-1, ASME, ASA-C-39.1-1984, FCC Part 15 Subpart J Class B,
NEC, OSHA, IEEE587, ANSI C 62.41-1980, ISO9000
FirstLine PL 10-40kVA Models
PL Model kVA/kW Internal Battery Time (minutes)
FLP-010-0
10kVA/9kW
0
FLP-010-1 37
FLP-010-2 18
FLP-010-3 9
FLP-015-0
15kVA/13.5kW
0
FLP-015-1 21
FLP-015-2 10
FLP-015-3 3
FLP-020-0
20kVA/18kW
0
FLP-020-1 14
FLP-020-2 6
FLP-030-0
30kVA/27kW
0
FLP-030-1 8
FLP-040-0
40kVA/36kW
0
FLP-040-1 4
Note: Longer battery run time available
For Frequency Converter add -FC to PL Model Number.