Owner manual

Gamatronic Electronic Industries Ltd.
POWER
+
RM
50 KVA, N.Am. Std. – User Guide, Release 1.9
51
5.11.1 Changing the Power+ output voltage
1. Press the Enter key to display the main menu, and then select SETUP:
1> SYSTEM 4> HISTORY 7> SETUP
2> UPS MODULE 5> BATTERY 8> STATIC SW
3> SELFTEST 6> ALARM 9> _____
NAVIGATE: <UP, DOWN> 1 SELECT: <ENTER>
Figure 44: Main menu
2. Enter the password. (The default password is pressing the "left-arrow" key eight times,
and then the Enter key:
[Main Menu > SETUP]
POWER+ System Setup
Type in Level-1 PASSWORD, THEN – ENTER
Your privilege will expire after 15 min.
PASSWORD:________
Figure 45: Level 1 password access
3. Select Module/s voltage:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 46: Module Config. setup menu
4. Use the ▲▼arrow keys to set the module/s voltage, press Ent, and then Esc:
[Main Menu > SETUP > (password) > Module conf. > Module/s voltage]
Module/s voltage 4: 118V
1: 110V 5: 120V
2: 113V 6: 125V
3: 115V (selected) 5: 130V
Figure 47: Setting the Module/s voltage