Installer Manual VENTILATION SYSTEMS VB0066 Model Numbers HRV-150 HRV-210 ERV-150 ERV-210 06786-04/12/22
Table of Contents 1.0 SERVICE ............................................................................................4 1.1 3-D Drawing ................................................................................4 1.2 Parts Ordering Chart ....................................................................5 1.3 Technical Support ........................................................................5 2.0 SIZING .....................................................................................
Table of Contents 8.0 INSTALLATION 8.1 8.2 8.3 8.4 9.0 (cont’d) OF THE CONTROLS ..................................................22 Dimensions and Specifications ................................................22 Installation of the Main Control ..........................................22-23 Electrical Connection to Optional Controls ..............................24 Electrical Connection to the Furnace ......................................24 WIRING DIAGRAM ...........................................
VL0018 5 4 3 1 2 7 12 11 10 9 8 13 18 14 25 6 24 VIEW) 23 16 17 19 15 20 22 3 21 1.1 21 DAMPER ASSEMBLY (REAR 1.
1.0 Service (cont’d) 1.2 PARTS ORDERING CHART No Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26* Double collar port #2 Wing nut #10-32 Balancing double collar port Inlet ring Motor assembly Electronic board V99 Square balancing damper Door latches (latch) Drain connector Drain gasket 0.
2.0 Sizing These are the two most common methods used to evaluate the ventilation needs of a house: CSA F326 and Canadian Building Code: • High speed: 10 cfm per room 20 cfm for the master bedroom and the basement • Low speed: 40-60% of high speed ASHRAE Standard 62-2001: • 0.35 air change per hour Refer to ventilation code of your area to determine which method to use.
JUNEAU • Extended Defrost setting not required (factory defrost strategy pre-set). • MODELS: HRV-150, HRV-210 ZONE B (HRVs only) SALEM OLYMPIA HAY RIVER PHOENIX SANTA FE see ZONE C SELECTION CHART beside • ERV MODELS: ERV-150, ERV-210. • ERVs: Set Defrost mode #1 according to section 6.1. ZONE D ERVs recommended) • HRV MODELS: HRV-150, HRV-210. • ERV MODELS: ERV-150, ERV-210.
4.0 Technical Data 4.1 AIR DISTRIBUTION (NORMAL OPERATION) Applicable to all model numbers. STALE AIR TO OUTSIDE FRESH AIR FROM OUTSIDE FRESH AIR TO BUILDING STALE AIR FROM BUILDING VF0013 4.
4.0 4.3 Technical Data (cont’d) PERFORMANCE CHARTS MODEL NUMBER: ERV-150 Electrical requirements: 120 volts, 1.3 Amps Exhaust Air Transfer Ratio: 0.06 225 External Static Pressure - Pascals (250 Pascals = 1” of water) 200 VENTILATION PERFORMANCE External Static Pressure Pa in. w.g. Net Supply Air Flow l/s cfm Gross Air Flow Supply Exhaust l/s cfm l/s cfm 25 50 75 100 125 150 175 200 81 78 72 67 55 46 36 30 87 83 76 71 59 49 39 32 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.
4.0 4.3 Technical Data PERFORMANCE CHARTS (cont’d) (CONT’D) MODEL NUMBER: HRV-150 Electrical requirements: 120 volts, 1.3 Amps Exhaust Air Transfer Ratio: 0.05 225 External Static Pressure - Pascals (250 Pascals = 1” of water) 200 VENTILATION PERFORMANCE External Static Pressure Pa in. w.g. Net Supply Air Flow l/s cfm Gross Air Flow Supply Exhaust l/s cfm l/s cfm 25 50 75 100 125 150 175 84 80 77 69 61 46 38 88 84 81 72 65 49 40 0.1 0.2 0.3 0.4 0.5 0.6 0.
4.0 4.4 Technical Data (cont’d) DIMENSIONS 6" (152mm) Model numbers: 13-3/4" (349mm) 30-1/4" (768mm) • ERV-150 • HRV-150 20" 0" (508mm) (50 2.5" (63mm) VK0040 Model numbers: 6" (152mm) 30-1/4" (768mm) 19" (483mm) • ERV-210 • HRV-210 20" (508mm) (50 08m 2.5" (63mm) VK0039 4.5 CONTROLS AND FURNACE LINK OPTION Main controls: • Basic Wall Control • Electronic Wall Control 4.
5.0 Typical Installation There are three (3) common installation methods. 5.1 FULLY DUCTED SYSTEM (Primarily for homes with radiant hot water or electric baseboard heating. See figure 1.) Moist, stale air is exhausted from the high humidity areas in the home, such as bathrooms, kitchen and laundry room. Fresh air is supplied to bedrooms and principal living areas. The use of bathroom fans and a range hood is suggested to better exhaust stale air.
6.0 Installation INSPECT • • • • THE CONTENTS OF THE BOX Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door latches, door hinges, dampers, duct collars, cabinet, etc. Inspect the interior of the unit for damage. Ensure that the fan motor assembly, recovery core, insulation, dampers, damper actuator and drain pan are all intact. If the unit was damaged during shipping, contact your local distributor.
6.0 6.3 Installation PLANNING OF THE (cont’d) DUCTWORK a) Follow the instructions in Section 6.4 below to determine the appropriate duct diameters for your system. b) Keep it simple. Plan for a minimum number of bends and joints. Keep the length of insulated duct to a minimum. c) Do not use wall cavities as ducts. Do not use branch lines smaller than 4” (102 mm) Ø. d) Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood.
6.0 6.4 Installation (cont’d) CALCULATING THE DUCT SIZE (CONT’D) 6.4.2 Example of a design for a fully ducted system for a unit having a high speed performance of 222 cfm (See figure 9). 4” 4” 5” 4” Ø 42 cfm 5” Ø 64 cfm 5” Ø 65 cfm 4” Ø 42 cfm 6” Ø 93 cfm 6” Ø 96 cfm 4” 6” 6” Ø 129 cfm 4” 6” Ø 84 cfm 6” 7” 7” 6” 6” 6” Ø 138 cfm 7” Ø 222 cfm VI0004 7” Ø 222 cfm figure 9 6.
6.0 Installation (cont’d) 6.5 Installing the Ductwork and Registers (cont’d) 6.5.2 Exhaust Ducted System (Source Point Ventilation) (as illustrated in Section 5.2) Stale air exhaust ductwork: (same as for Fully Ducted System, described on page 15) Fresh air distribution: 010 ! WARNING When performing duct connection to the furnace, installation must be done in accordance with all applicable codes and standards. Please refer to your local building code.
6.0 Installation (cont’d) 6.5 Installing the Ductwork and Registers (cont’d) 6.5.3 Simplified installation (Volume Ventilation) (as illustrated in Section 5.3) 010 ! WARNING When performing duct connection to the furnace, installation must be done in accordance with all applicable codes and standards. Please refer to your local building code. CAUTION When performing connection to the furnace ducts (Method 1), these ducts must be sized to support the additional airflow produced by the HRV/ERV.
6.0 6.6 Installation (cont’d) CONNECTING DUCTS TO THE UNIT Insulated flexible duct Use the following procedure for connecting the insulated flexible duct to the ports on the unit (exhaust to outside and fresh air from outside). a) b) c) d) e) f) Pull back the insulation to expose the flexible duct. Connect the interior flexible duct to the port using a duct tie. Carefully seal the connection with duct tape.
6.0 6.7 Installation (cont’d) INSTALLING THE EXTERIOR HOODS CAUTION All models require an exhaust hood with a backdraft damper. This damper closes when the unit is off and prevents unwanted cold air from entering the house. Choose an appropriate location for installing the exterior hoods: • a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination • a minimum distance of 18 inches (457 mm) from the ground Make sure the intake hood is at least 6 feet (1.
7.0 7.1 Control Devices Main Controls CAUTION All models require a main control. Basic model Electronic model CONDENSATI0N CONTROL CONDENSATI0N CONTROL ER MM SU ER MM SU -20 C -4° CO F °C -4°F E Z N 41°F CO M ZO -5 E C 41°F AIR SUPPLY L CONTROL CONDENSATION CONTROL MAXIMUM SPEED OFF AIR EXCHANGE IN PROGRESS AIR SUPPLY L CONTROL MIN. AIIR R EXCHANGE CH HA MIN. MAX. 20 M MIN. N ON MAX. CONTINUOUS VC0028 VC0027 Modes MODELS Indicators Detector types Switches 7.2 40 M MIN.
7.0 7.3 Control Devices (cont’d) OTHER FEATURES FURNACE INTERLOCK (for forced air heating system) The furnace fan can be interlocked so that it will run simultaneously with the ERV or HRV to ensure proper distribution of fresh air throughout the house (see table section 7.4, to see if it is available on your unit). PERMANENT MEMORY Our electronic controls have a default memory feature in the event of a power outage.
8.0 8.1 Installation of the Controls DIMENSIONS AND SPECIFICATIONS (MAIN CONTROLS) Voltage: 12 volts DC Dimensions: 5” x 5” x 1 3/8” 13/8" (35 mm) 5" (127 mm) (127 mm x 127 mm x 35 mm) 5" (127 mm) VC0016 FRONT VIEW 8.2 INSTALLATION OF THE (BASIC AND ELECTRONIC) SIDE VIEW MAIN CONTROL CAUTION Never install more than one main control per unit. INSTRUCTIONS: 1- Determine the location of the control. The wall control must be installed in a central location on the main floor.
8.0 8.2 Installation of the Controls INSTALLATION OF THE (cont’d) MAIN CONTROL (cont’d) Y R GB VD0026 4- Connect the wires to the main control. (See figure 17.) figure 17 5- Make sure the instruction pull-out is in the occupant’s language. If not, turn it to the other side. (See figure 18.) 6- Reinstall the cover plate and the button(s). figure 18 VC0061 7- Connect the wires to their corresponding position inside the electrical compartment.
8.0 8.3 Installation of the Controls (con’d) ELECTRICAL CONNECTION TO OPTIONAL CONTROLS MAIN PC BOARD 9 8 7 6 OL 5 OC 4 I 3 2 1 J3 J1 1 4 7 2 5 8 3 6 9 0L 8.4 REAR VIEW PUSH-BUTTON SWITCHES (5 switches maximum) VE0036A I ELECTRICAL CONNECTION TO THE FURNACE 010 ! WARNING Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control.
-t° 25 BK O NO BK BL BN G GY BLACK BLUE BROWN GREEN GREY DOOR INTERLOCK SWITCH S1 COM BL Y M2 BL DAMPER BL MOTOR LINE BK W G 6- The furnace fan circuit must be class 2 circuit only. 5- The field wiring must comply with applicable codes, ordonnances and regulations. 4- Use the factory supplied protective tubing. 3- If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.
10.0 Air Flow Balancing WHAT YOU NEED TO BALANCE THE UNIT LOW • A magnehelic gauge capable of measuring 0 to 0.25 inch of water (0 to 62.5 Pa) and 2 plastic tubes. Two ”Flow Measuring Stations” or two flow collars (the size will vary depending on the duct diameter). HIGH FLOW • LOW H W VP0006 VP0005 Flow collar Flow measuring station PRELIMINARY STAGES TO BALANCE THE UNIT • Seal all the unit ductwork with tape. Close all windows and doors.
10.0 Air Flow Balancing (cont’d) BALANCING PROCEDURE 1. Set the unit to high speed. Make sure that the furnace blower is ON if the installation is in any way connected to the ductwork of the cold air return. If not, leave furnace blower OFF. If the outside temperature is below 0°C / 32°F, make sure the unit is not running in defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a defrost cycle.) 2.
11.0 Overall Verification 11.1 MAIN CONTROLS This procedure allows the installer to verify that all modes of operation are fully functional. During the verification of a main control, make sure that all optional remote controls are inactive.
12.0 Maintenance / Instructions for User 010 ! WARNING Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source. • Review with the user the steps required for the regular maintenance of her/his ventilation system. These steps are described in details in the user manual: FOUR TIMES A YEAR: • • • • Inspect the intake hood, and clean if needed. Clean the filters. Clean the interior of the cabinet and clean the door.
13.0 Troubleshooting NOTE: Inspect the unit before proceeding with these steps. Start-up troubleshooting: Problems Possible causes 1. Unit does not work. • The circuit board may be defective. You should try this B G VE0082 • Unplug the unit. Disconnect the main control and the optional(s) control(s) (if need be). Jump B and G terminals. Plug the unit. If the motor runs on high speed and the damper opens, the circuit board is not defective. 2. The damper actuator does not work.
13.0 Troubleshooting Problems (cont’d) Possible causes You should try this 4. The 20-minute push-button • The switch or the 20/40/60-minute may be defective. push-button timer does not workOR its indicator light does not stay on. OL OC VE0067 • Unplug the unit. Disconnect the main control and the optional(s) control(s) (if need be). Jump the OL and OC terminals. Plug the unit. If the unit switches to high speed, replace the switch. 5.
14.0 Warranty The standard warranty for the HRV or ERV unit is one year parts only. If this product was installed with a matched MAYTAG system, it carries a 10-year parts only warranty. 15.0 References • HVI, “Installation Manual for Heat Recovery Ventilators”, 1987 edition. • ASHRAE 1984 Systems Handbook, chapter 11, “Air Distribution Design for Small Heating and Cooling Systems”.