VENTING DESIGN SPECIFICATIONS 
This section is intended for architectural designer and builder/ 
contractor reference only.
NOTES:
 ■ Vent materials needed for installation are not provided 
with microwave hood combination.
 ■ We do not recommend using a  exible metal vent.
 ■ To avoid possible product damage, be sure to vent air 
outside, unless using recirculation installation. Do not 
vent exhaust air into concealed spaces, such as spaces 
within walls or ceilings, attics, crawl spaces or garages.
For optimal venting installation, we recommend:
 ■ Using roof or wall caps that have backdraft dampers.
 ■ Using a rigid metal vent.
 ■ Using the most direct route by minimizing the length 
of the vent and number of elbows to provide ef cient 
performance.
 ■ Using uniformly sized vents.
 ■ Using duct tape to seal all joints in the vent system.
 ■ Using caulking compound to seal exterior wall or roof 
opening around cap.
 ■ Not installing two elbows together, for optimal hood 
performance.
If venting through the wall, be sure that there is proper clearance 
within the wall for the damper to open fully.
If venting through the roof, and rectangular-to-round transition is 
used, be sure there are at least 3" (7.6 cm) of clearance between 
the top of the microwave oven and the transition piece. See 
“Rectangular-to-Round Transition” illustration.
Rectangular-to-Round Transition
NOTE: The minimum 3" (7.6 cm) clearance must exist between 
the top of the microwave oven and the rectangular-to-round 
transition piece so that the damper can open freely and fully.
Recommended Standard Fittings
The following length equivalents are for use when  guring vent 
length. See the examples in “Recommended Vent Length.”
Roof venting Roof cap
A
B
C
E
F
D
3" (7.6 cm)
A. Roof cap
B. 6" (15.2 cm) minimum diameter round vent
C. Elbow (for wall venting only)
D. Wall cap
E. 3
1
⁄
4
" x 10" to 6" (8.3 x 25.4 cm to 15.2cm) 
rectangular-to-round transition piece
F. Vent extension piece, at least 3" (7.6 cm) high
AB C
DE FG
A. Rectangular-to-round transition piece: 3
1
⁄
4
" x 10" to 6" = 5ft 
(8.3 x 25.4 cm to 15.2 cm = 1.5 m)
B. Roof cap: 3
1
⁄
4
" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)
C. 90° elbow: 3
1
⁄
4
" x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)
D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)
E. Wall cap: 3
1
⁄
4
" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)
F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)
G. 90°  at elbow: 3
1
⁄
4
" x 10" = 10 ft (8.3 x 25.4 cm = 3 m)
Wall venting Wall cap