Install Instructions

A
a. Cover Removal and Installation Procedure
For FS7-4 models with NEMA 1 Enclosure
Using a flathead screwdriver, loosen but do not remove the
two cover screws and remove the cover (A).
Place the cover on the flow switch sliding the slots behind
the two loose cover screws. Push the cover down into the
flow switch and using a flat blade screwdriver, tighten the
cover screws to a torque of 10 lb•in (1.13 N•m).
For FS7-4W & FS7-E models
Using a 5/16” socket wrench, unscrew the six bolts that
secure the switch housing and remove cover.
FS7-4W models have gasket that needs to be removed
and replaced.
Place cover on flow switch and use 5/16” socket wrench
to tighten the six bolts to 5 ft•lb (7 N•m) torque.
STEP 4 - Electrical Installation
To prevent electrical shock, turn off the electrical power before making electrical connections.
To prevent an electrical fire or equipment damage, electrical wiring insulation must have a rating of 167˚F
(75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).
To prevent electrocution, when the electrical power is connected to the flow switch, do not touch the
terminals.
Make sure flow switch electrical cover is secured before turning on electric power.
Failure to follow this warning could cause property damage, personal injury or death.
7
!
WARNING