Install Instructions
A
a. Cover Removal and Installation Procedure
For FS7-4 models with NEMA 1 Enclosure
• Using a flathead screwdriver, loosen but do not remove the
two cover screws and remove the cover (A).
• Place the cover on the flow switch sliding the slots behind
the two loose cover screws. Push the cover down into the
flow switch and using a flat blade screwdriver, tighten the
cover screws to a torque of 10 lb•in (1.13 N•m).
For FS7-4W & FS7-E models
• Using a 5/16” socket wrench, unscrew the six bolts that
secure the switch housing and remove cover.
• FS7-4W models have gasket that needs to be removed
and replaced.
• Place cover on flow switch and use 5/16” socket wrench
to tighten the six bolts to 5 ft•lb (7 N•m) torque.
STEP 4 - Electrical Installation
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• To prevent an electrical fire or equipment damage, electrical wiring insulation must have a rating of 167˚F
(75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).
• To prevent electrocution, when the electrical power is connected to the flow switch, do not touch the
terminals.
• Make sure flow switch electrical cover is secured before turning on electric power.
Failure to follow this warning could cause property damage, personal injury or death.
7
!
WARNING