INSTALLATION –
TOOLS NEEDED:
One (1) pipe wrench and one (1) socket wrench.
STEP 1 - Preparation
A
Drain the water in the receiving tank to a level
which is below the control opening (A). Allow the
boiler to cool to 80˚F (27˚C) and allow the
pressure to release to 0 psi (0 bar).
C
D
Use a socket wrench to secure the feeder (D)
to the receiver tank with the six
3
/8” - 16
bolts through mounting flange (C) and
tighten to 18 ft•lb (24 N•m).
STEP 2 - Install the Control Unit
Mounting Flange Dimensions
B.C.
O.D.
Float
O.D. B.C. C D Diameter
6
11
⁄16 (170) 5
3
⁄4 (146) 6
7
⁄16 (11.1) 4
3
⁄4 (121)
Series 851, 851-S and 847
Dimensions, in. (mm)
“C” - number of mounting holes
“D” - size of mounting holes